Figure 3-4 Setup Procedure for Sub-Cooling Method
POWER ON the Vortex AC and ROTATE the DISCHARGE Valve (V3) to
achieve a pressure differential of at least 100 PSIG between the LP Gauge
and the HP Gauge. KEEP THE HP BELOW 550 PSIG on the HP Gauge to
ensure that the HP Cutoff Switch will not actuate.
After several minutes of running, the tank will be cold. POWER OFF the Vortex
AC and reconfigure the setup for NORMAL RECOVERY. Repeat as needed.
3.6 Special Operating Notes
During normal operation, when the High Pressure switch activates the
machine will restart automatically when the head pressure drops below
approximately 425 PSI.
When the Tank Over Fill Protection Device (OFPD) is installed, the yellow
“Tank Full” signal light will be illuminated when the OFPD cable is not
connected or when the tank is full.