Johnson Systems CD-3000 Series Retrofit Control System User Manual

Page 5

Advertising
background image

www.johnsonsystems.com

5

• Unscrew the two mounting (thumb) screws that hold the old processor

housing in place. Slowly remove the old card cage, taking care not to

strain or disconnect any of the original CD-80

®

wiring. Carefully observe

and label as necessary all wiring as to its location and polarity.

• If you are not familiar with the Strand CD-80

®

dimmer rack processor

electronics and wiring, it is strongly advised that you take a few minutes

to look at the back of the processor housing connections and compare it

to the backplane on the CD-3000-AE. Do not disconnect any wiring until

you are satisfied with how easy this is going to be.

NOTE: Never pull directly on the wires to remove connectors.
• Disconnect the power connector. This connector is a 9-position CPC

(Circular Plastic Connector) plug (female - cable mount) and receptacle

(male - chassis mount). It is black in color and approximately two (2)

inches in length. It is located at the lower (rear) right-hand side of

the old processor housing. Turn the locking ring counterclockwise to

disconnect.

• Disconnect the four (4) 27-conductor control output cables. Do not pull

on the wire to disconnect. Carefully apply pressure to the connector

itself with either your fingers or preferably a small flat head screwdriver.

Do not mix up the cable order or polarity.

• Disconnect the smaller 10-conductor connector. This connector and

cable is not required on the CD-3000 retrofit and should be coiled up

and wire-tied. Carefully set it aside inside the rack and keep it isolated

from any AC line voltage.

• The old processor housing can now be set aside.

Installation of the new CD-3000-AE System

• Remove your new CD-3000-AE system from the box. Leave the foam

end caps in place to protect the unit from damage.

• Familiarize yourself with the backplane, and low voltage control input/

output connections. Refer to page 12 for details.

• Dress out all DMX and other low voltage connections to the backplane

using the breakaway connectors provided. Be sure to isolate and protect

all shield wires.

• Place the CD-3000-AE in front of the rack face down / backplane up.

Leave the foam end caps left in place to protect the unit from

damage.

• Connect the four (4) 27-conductor control output cables to the

backplane in the same order and polarity in which they were

removed. Extra care should be taken not to bend or break any

of the connector/header pins. Damage to these pins may require

replacement of the entire CD-3000 assembly and will not be considered

warranty! Refer to page 10 for the connector pinout.

• Connect all other applicable low voltage control input/output connections

to the backplane.

• Connect the 9-position CPC power connector. The connector is

keyed, so the plug and receptacle must be aligned to mate properly.

Once aligned, turn the locking ring clockwise until a “click” is heard and

felt indicating that the connector is fully seated. Refer to page 10 for the

connector pinout.