2.5. Cooling

water

connection

Only for water cooled models - FLW:

Cooling water pressure (IN / OUT )

max.

6 bar

Difference pressure (IN - OUT )

2 bar to 6 bar

Flow rate on FLW 20006

typical

24.0 l/min

Cooling water temperature

15 °C

Notice:

Cooling water circuit

Risk of oil leaking from the refrigeration system (compressor) of the recirculating
cooler into the cooling water in case of a fault in the cooling water circuit!
Observe the laws and regulations of the water distribution company valid in the
location where the unit is operated.

Recommended quality of cooling water:

pH – value

7,5 to 9,0

Sulfate [SO4 2- ]

< 100 ppm

Hydrocarbonate [HCO3- ] / Sulphate [SO4 2-]

> 1 ppm

Hardness [Ca2+, Mg2+] / [HCO3-]

> 0,5 dH

Alkalinity

60 ppm < [HCO3-] < 300 ppm

Conductivity

< 500 μs / cm

Chloride (CL-)

< 50 ppm

Phosphate (PO43-)

< 2 ppm

Ammonia (NH3)

< 0,5 ppm

Free Chlorine

< 0,5 ppm

Ferri Ions (Fe3+ )

< 0,5 ppm

Mangano Ions (Mn2+)

< 0,05 ppm

Carbon dioxide (CO2)

< 10 ppm

Hydrosulfide (H2S)

< 50 ppm

Content of oxygen

< 0,1 ppm

Algae growth

impermissible

Suspended solids

impermissible


Notice:

Danger of corrosion of heat exchanger due to unsuitable quality of cooling
water.
 Due to its high content of lime hart water is not suitable for cooling and causes

calcination of the heat exchanger.

 Ferrous water or water containing ferrous particles will cause formation of rust

even in heat exchangers made of stainless steel.

 Chlorous water will cause pitting corrosion in heat exchangers made of stainless

steel.

 Due to its corrosive characteristics distilled and deionized water is unsuitable and

will cause corrosion of the bath. .

 Due to its corrosive characteristics sea water is not suitable.

 Due to its microbiological (bacteria) components which settle in the heat

exchanger untreated and unpurified river water and water from cooling towers is
unsuitable.

 Avoid particulate matter in cooling water.

 Avoid putrid water.