4 replacing the two semiconductor fuses, Replacing the two semiconductor fuses, 4 electrical connection – JUMO 709050 IPC IGBT Power Converter IPC 200A Operating Manual User Manual

Page 27

Advertising
background image

IGBT Power Converter 200A [Patent No. EP1 126 591 B1] 02.08

27

4 Electrical connection

4.1.4 Replacing the two semiconductor fuses

h Disconnect (all poles) the converter from the voltage supply.
h Wait 1 minute to allow hazardous voltages to discharge.
h Check that no voltage is present on the screw terminals.
h Open the housing as described in Chapter 3.4.1 „Opening the housing“.

h Undo the 2 screws each for the left and right semiconductor fuse and take

the fuse out of its holder.

h Replace blown fuses with new ones and retighten the screws at a max.

tightening torque of 20 Nm.

h Remedy the cause that led to the semiconductor fuse tripping (e.g. earth

short in the power section).

h Only use original JUMO replacement parts, item No. 70/00434229.
v Chapter 2.3.2 „Required accessories“

Advertising