7 technical data – JUMO 709040 TYA-110 thyristor power unit Operating Manual User Manual

Page 52

Advertising
background image

7 Technical data

52

Power units 02.06

Actual (power) output

V

2

signal as standard.

With extra code TR or TO: free choice between V

2

, P, or I

2

signal via internal

switches, adjustable from 0 — 5V to 0 — 10V. I

max

≈ 2mA.

Electrical connection Control wiring by screw terminals for conductor cross-sections 0.2 — 2.5mm

2

.

Load connections by cable lugs to DIN 46 212.

Protection

IP00 as per EN 60 529, heatsink is grounded

Permitted ambient
temperature range

0 — 45°C

Permitted current derated by 2% for each °C increase in ambient temperature;

the maximum permissible ambient temperature must not exceed 60°C.

Permitted storage
temperature range

-10 to +70°C

Climatic conditions

rel. humidity

≤ 75% annual mean, no condensation

Cooling

natural convection

Operating position

vertical

Operating conditions

The thyristor power unit is designed as a built-in unit to:

VDE 0160 5.5.1.3 (5/88)

VDE 0106 Part 100 (3/83)

pollution degree 2 to VDE 0110 Part 1 4.2 (1/89)

overvoltage category Ü III to VDE 0160 5.7 (5/88)

Test voltage

to VDE 0160 Table 4 (6/88)

Electromagnetic
compatibility

Control electronics to EN 61 326

Creepage distance

control electronics to load circuit

≥ 10mm

control electronics to housing

≥ 10mm

Unit can be connected to SELV circuits.

SELV = Seperate Extra Low Voltage

Housing

TYA110/3,

25 (50)

110 x 195 x 152mm

TYA110/3,

75 (100)

125 x 195 x 170mm

TYA110/3, 150

(250)

150 x 220 x 280mm

Weight

TYA110/3,

25 (50)

2.8 kg

TYA110/3,

75 (100)

3.7 kg

TYA110/3, 150

8.6

kg

TYA110/3

250

9.0 kg

Standard
accessories

1 mounting plate for wall-mounting

1 Operating Instructions B 70.9040