6 technical data (extract from data sheet) – JUMO 706581 LOGOSCREEN nt stainless steel front Installation Instructions User Manual

Page 35

Advertising
background image

35

6 Technical data (extract from data sheet)

Transducer short circuit/break

Binary inputs/outputs (option)

Outputs

Interfaces

Short-circuit

1

Break

1

Thermocouple

not detected

detected

Resistance thermometer

detected

detected

Resistance transmitter

not detected

detected

Potentiometer

not detected

detected

Voltage

≤ ± 210mV

not detected

detected

Voltage > ± 210mV

not detected

not detected

Current

not detected

not detected

1

Programmable reaction of device, e.g. triggering alarm

Input or output

configurable as input or output

Number

8, 16 or 24, depending on the device version,

to DIN VDE 0411, Part 500; max. 25Hz, max. 32V

Input

- level

logic "0": -3 to +5V (input current max. ±1mA),

logic "1": 12 to 30V (2.5mA

≤ input current ≤ 5mA)

- counting frequency

8Hz

High-speed input

the first two binary inputs of each module (B1, B2, B9, B10, B17, B18),

if the module is not fitted with relays or 6 analog inputs

- task

count function, e.g. for flow measurement

- counting frequency

10kHz

Output

- type

open-collector output, switches relative to positive voltage

- level

logic "0": transistor is inhibited

(max. permissible voltage across switching transistor 30V, max. leakage current 0.1 mA)

logic "1": transistor is switched on

(max. voltage across switching transistor 1.6V, max. current 50 mA)

- sampling cycle

at least 1sec (1Hz)

1 relay (ex-factory)

changeover (SPDT), 3A, 230V AC

1

6 relays (option)

changeover (SPDT), 3A, 230V AC

1,2

1

With resistive load.

2

It is not permissible to mix SELV circuits and supply circuits.

RS232/RS485 (connector 7)

- protocol
- baud rate
- modem
- connector
- external inputs

Qty. 1, switchable between RS232 and RS485

Modbus master, Modbus slave and barcode reader

9600, 19200, 38400

can be connected

SUB-D

via the Modbus master/slave function, 24 analog and 24 binary

RS232 for barcode reader (connector 2)

- protocol
- baud rate
- connector
- external inputs

Qty. 1

Modbus master, Modbus slave and barcode reader

9600, 19200, 38400

SUB-D

via the Modbus master/slave function, 24 analog and 24 binary

Ethernet (connector 6)

- quantity
- protocols
- baud rate
- connector
- data format

max. 1

TCP, IP, HTTP, DHCP, SMTP, ModbusTCP

10Mbits/sec, 100Mbits/sec

RJ45

HTML

USB host (connector 5)

- quantity

- use
- max. current

2 (or 1 with stainless steel front),

connector 5 and front connector (not with stainless steel front); no parallel operation

for connecting a memory stick

100mA

USB device (connector 15)

- quantity

- use

2 (or 1 with stainless steel front),

connector 15 and front connector (not with stainless steel front); no parallel operation)

for connecting to the (master) computer