Data Sheet 603031

2013-03-08/00309799

Page 3/6

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Operating data

Case

Process connection

Note:
Physical and toxic features of the expansion means, which could occur in the event of a measuring system break.

1

There is currently no statement by the health authority concerning hazards to health in the event of short-term exposure
and low concentration, e.g. measuring system break.

Hysteresis
in % of the control /
limit value range

Rated value

Possible process value

Designation

3

3-4

S1

6

6-8

S2

1.5

1-2

S3

Switching point accuracy
in % of the control/limit val-
ue range

TW: in the upper third of the scale ± 1.5%

STB, STW (STB): in the upper third of the scale +0/-5%

Ambient temperature in-flu-
ence referring to the con-
trol /
limit value range

When the ambient temperature on the case deviates from the calibration ambient temperature 22 °C,

a switch point offset occurs.

Higher ambient temperatures = lower switching point

Lower ambient temperature = higher switching point

For devices with scale limit value

< 200 °C

÷ 200 °C

ATH.-SE-2

ATH.-SE-20
ATH.-SE-70

ATH.-SE-2

ATH.-SE-20
ATH.-SE-70

on case

0.08%/K

0.17%/K

0.06%/K

0.13%/K

on capillary per m

0.047%/K

0.054%/K

0.09%/K

0.11%/K

admissible storage tem-
perature

-50 to 50 °C

admissible ambient
temperature during use

max. +80 °C

Rated position

as per DIN 16 257, NL 0 to NL 90 (different rated positions (NL) on request)

Case

Aluminum die cast case

Surface with impact resistant textured paint:

Lid: RAL 7032, bottom section: RAL7015

Set point adjustment

The switching point can be adjusted by means of a screwdriver once the case lid has been removed

Protection class

EN 60 529-IP 54

Weight

ATHf-SE-... approx. 0.70 kg
ATHs-SE-...approx. 0.65 kg with screw-in sheath "20“
ATHs-SE-...approx. 0.85 kg with screw-in sheath and intermediate piece "30“

Type series
ATHs-SE-..
with rigid shaft

Scale limit value up to 150 °C

Sheath "20“

Scale limit value exceeding 150 °C

Sheath "30“

Screw-in sleeve with screw-in spigot G 1/2

form A as per DIN 3852/2

Screw-in sleeve with screw-in journal G 1/2

form A as per DIN 3852/2

and intermediate piece

to ensure that the max. admissible ambient temperature

of +80 °C is not exceeded on the case

Type series
ATHf-SE-..
with capillary

plain cylindrical probe "10“ (standard)

Screw-in sheath "20" (on request)

Screw-in sleeve with screw-in spigot G 1/2 form A as per DIN 3852/2

and clamping piece with locking screw to lock the probe

Material

Sheath "20“

Sheath "30“

up to +150 °C CuZn as standard

over +150 °C CrNi as standard

over +150 °C CrNi as standard

Fitting length S
(max. 200 mm)

Standard lengths: 100, 120, 150 (material CuZn, CrNi)

with 200 mm CuZn only

Immersion tube Ø

D = 8 mm, D = 10 mm

Control range

with scale limit value

Hazardous re-

actions

Fire and explosion hazard

hazardous

to waters

Information about toxicology

Ignition

temperature

Explosion limit

irritant

dangerous to

health

toxic

< +200 °C

no

+ 355 °C

0.6 -8 V%

Yes

Yes

1

no

200 °C

≤ +300 °C

no

+ 490 °C

- -

Yes

Yes

1

no