8 Programming examples

8.4

Heartbeat Producer Time

(see Chapter 5.7 “Heartbeat”, page 20)

Alteration of the time for the cyclic transmission of a sign of life at 5000msec
intervals (1388hex)

8.5

Boot mode “Minimum bootup”

(see Chapter 5.2 “NMT”, page 15)

After switch-on, the transmitter should adopt the preoperational state.

A change of boot mode only becomes effective after a reset !

8.6

Event time

(see Chapter 5.5 “PDO”, page 17)

Set the time for cyclic measurement transmission to 2000msec (7D0hex)

Node ID:

125

dec

COP ID:

67D

hex

Object index: 1017

hex

Subindex:

00

hex

Value:

1388

hex

Node ID:

125

dec

COP ID:

67D

hex

Object index: 1F80

hex

Subindex:

00

hex

Value:

0C

hex

Node ID:

125

dec

COP ID:

67D

hex

Object index: 1800

hex

Subindex:

05

hex

Value:

7D0

hex