Kees DFG (DIRECT FIRED GAS) MAKE-UP AIR UNITS User Manual

Page 13

Advertising
background image

12

G.

UNIT UNDER-FIRED (Temperature
Rise Too Low)

REMEDY

Probable

1.

Lack of gas pressure.

Adjust gas pressure as stated on

Cause:

unit identification plate.

2.

Lack of static external

Adjust motor sheave to

pressure.

decrease blower RPM or adjust
temperature rise using regulator
inside unit.

3.

Gas line obstruction.

Remove obstruction.

4.

Dirty burner.

Clean burner.

5.

Defective gas valve.

Replace valve.

6.

Improper adjustment of

Adjust temperature rise per

temperature rise.

start-up card or instruction in
manual.

____________________________________________________________________

H.

BURNER WON'T MODULATE --
ELECTRONIC CONTROL SYSTEMS

1.

Refer to Maxitrol Series 14 Installation, Instruction and Field
Service Check List included in the next pages of this manual.