System Diagram

Condenser Fans

LED Display Panel

Carrying Handles

Control Panel

Power Switch

Fill Port

Coolant Inlet

& Outlet

Power Connection

Relay & Thermocouple

Terminals (Optional)

Reservoir Level

Drain Plug

CAUTION:

Always keep the EXC-800 chiller upright during operation.

Additionally, THE UNIT MUST BE KEPT UPRIGHT FOR AT LEAST
24 HOURS BEFORE POWERING ON. This is to allow enough oil to
reach the compressor. Powering-on the unit too early can permanently
damage the compressor and is not covered by the product warranty.

!

Positioning the System

The chiller must be run upright at all times. Upon arrival of this product via
transport or courier shipping, it must be kept upright FOR AT LEAST 24
HOURS BEFORE BEING POWERED ON

to

allow enough oil to reach the

compressor.

OK!

NO!

NO!

External Fittings

Install the G 1/4 BSPP threaded fittings
you purchased for your cooling system. It’s
recommended to hand-tighten all fittings to
avoid damaging the cooling unit.

Parallel threads seal at the included o-ring.
Do not use any plumber’s tape or putty on
the threads, which can interfere with the
o-ring seal.