Technical data, General data and operating conditions, 4technical data – Lenze CS9800 Operating Instructions User Manual

Page 26

Advertising
background image

Technical data

General data and operating conditions

4

l

26

BA_CSx8xx EN 3.0

4

Technical data

4.1

General data and operating conditions

General data

Conformity and approval

Conformity

CE

EN 61000−6−4
EN 61000−6−2

EMC Directive Class A, industrial premises

Approbation

UR

UL 508
CSA C22.2

Programmable Controllers (File−No. E236341)

Other

RoHS

Products lead−free in accordance with CE Directive
2011/65/EU

Protection of persons and equipment

Safety

VDE0805 (EN60950),
VDE0870, UL

Enclosure

Standard device

EN 60529

IP65

UL 508 (NEMA 250)

Type 1 enclosure pollution degree 2

Add−on components

EN 60529

IP65

Class of protection

3

EMC

Noise emission

EN 61000−6−4

Class A (industrial premises)

Noise immunity Zone B

EN 61000−6−2

Industrial premises

EN 61000−4−2

ESD; severity: 3, i.e.
8 kV in the case of air discharge,
4 kV in the case of contact discharge

EN 61000−4−3

RF interference (housing)
80 MHz … 1000 MHz, 10 V/m 80 % AM (1 kHz)

EN 61000−4−4

Burst, severity: 3

EN 61000−4−5

Surge, severity 3 *

EN 61000−4−6

RF conducted
150 kHz … 80 MHz, 10 V/m 80 % AM (1 kHz)

*

Due to the high−energy single current pulses, a surge requires a suitable external connection with lightning
protection elements like for instance lightning conductors and overvoltage arresters.