3 technical data, Technical data, Technical data 3 – Lenze EMF2177IB User Manual
Page 19
Advertising
Technical data
3
EDK2177DB DE/EN/FR 3.1
19
l
H1_Daten−2177_Kabeltyp
3
Technical data
Bus cable length
Depending on the data transmission speed set, the following distances may not be
exceeded in the case of a CAN bus (network topology: line):
Field
Values
Baud rate [kbit/s]
20
50
125
250
500
1000
Max. bus length [m]
3264
1284
492
228
96
30
Current consumption
The current consumption of the PC system bus adapter is effected via the USB connection,
current consumption: 200 mA.
Specification of the transmission cable
Use the cable type specified by the CiA organisation (CAN in automation).