Mounting the dynamic braking module, External resister assemblies, Tcf series drives – Lenze TC Series dynamic brake with external resistors User Manual

Page 2: Selecting external resistors

Advertising
background image

Lenze Americas • 630 Douglas Street • Uxbridge MA 01569 • USA

Sales (800) 217-9100 • Service (508) 278 9100 • www.lenzeamericas.com

DG01C

13360068

4.06"

2.00"

GND

4.6"

FRONT

VIEW

3.1"

3.1"

SIDE VIEW

MOUNTING THE DYNAMIC BRAKING MODULE

The diagram to the right illustrates how to mount the DB Module. The DB
Module is compatible with the DIN Rail Mounting Kit option, or can simply be
mounted to a flat surface such as an electrical panel.
NOTE: DO NOT mount the resistors below the drive! The resistors generate
heat, and must be mounted above or to the side of the drive.

DIN RAIL

BRACKET

DB MODULE

WARNING!

Hazard of electric shock! External resistors are connected to the drive's DC bus, which can reach 950 VDC. Connections to external resistors must be
electrically insulated and mechanically shielded for safety. High Voltage warning signs are also recommended.

EXTERNAL RESISTER ASSEMBLIES

HP

240/200 Vac

480/400 Vac

590/480 Vac

0.25 - 0.5

841-001

841-002

N/A

1 - 1.5

841-002

841-002

841-001

2

841-003

841-003

841-002

3

841-005

841-005

841-004

5

841-006

841-006

841-005

7.5 - 10

841-007

841-007

841-008

15 - 20

841-009

841-009

841-010

25 - 30

N/A

841-011

841-012

NOTE: These resistor assemblies are the same as those used with the MC
Series drives.

The DB Module does not include short-circuit protection for the

external resistors. If short-circuit protection is desired, fusing must be supplied
by the customer. Consult Lenze AC Tech.

EXTERNAL
RESISTORS
(SEE NOTE 3)

42

46

47

43

DB OPTION MODULE

14

GND

B -

B + R +

R -

B -

B +

TCF DRIVE

11

NOTE 2:

Use minimum 14 AWG wire for connections to B+, B-, R+, and R-. Tighten the DB module terminals to a torque of 2 lb-in (0.2 Nm), and
tighten the drive terminals to 4.5 lb-in (0.5 Nm). The B+ and B- wires MUST be twisted together and must be less than 12 inches long.
Twisting the R+ and R- wires is also recommended.

NOTE 3:

External resistors (see selection chart below) are required when using Dynamic Braking modules 845-200, 845-400, and 845-500. Only AC
Tech supplied resistors are approved for use with 845 dynamic braking modules.

TCF SERIES DRIVES

PROGRAMMING
1. Set Parameter 06 (TB-14 OUTPUT) to DB BRAKE (11).
WIRING

The diagram to the right illustrates how the DB module is wired to the TCF
drive.
Refer to important wiring NOTES herein.

NOTE 1:

Use 18 AWG wire for control connections. Tighten DB module and drive
control terminals to a torque of 2 lb-in (0.2 Nm). Overtorque of terminals
can result in damage.

SELECTING EXTERNAL RESISTORS

Use the chart below to select the proper external resistor assembly:

Advertising
This manual is related to the following products: