Main-bus connector type e82zwkn2, Stop – Lenze E82ZWKN2 User Manual

Page 3

Advertising
background image

Main-bus connector type E82ZWKN2

MAE82ZWKN2 2.0

l

Lenze Drive Systems GmbH, Postfach 10 13 52, D-31763 Hameln

( (+49) 5154 82-0, Fax Service: (+49) 5154 82-1112

These Instructions

Ÿ inform about the use of mains-bus connectors E82ZWKN2 and describe how to install them.

Ÿ are only valid

- for mains bus connectors E82ZWKN2 for 8200 motec frequency inverters, type E82MVxxx_2B

(0.25 kW and 0.37 kW).

- together with the Mounting Instructions EDKMV3 for 8200 motec.

The Mounting Instructions EDKMV3 delivered together with the 8200 motec inform about electrical

installation and commissioning.

Connection conditions

Ÿ Sum of mains currents max. 16 A!

Ÿ Cable cross-sections and fuses F1 must match the sum of mains currents.

Max. cable cross-section: 2.5 mm

2

(AWG14).

Ÿ Max. 4 motec can be connected in parallel.

Ÿ The discharge current to earth is higher than 3.5 mA. Therefore permanent installation is required.

8200 motec

Mains contactor K10 required for connection of:

Type

Mains current

2 motec

3 motec

4 motec

E82MV251_2B

3.4 A

11 kW*

15 kW*

22 kW*

E82MV371_2B

5.0 A

11 kW

4 kW**

15 kW

4 kW**

22 kW

4 kW**

*

Mains contactor determined by switch-on current

**

With external switch-on current limitation, type E82ZJ004

Observe national and regional regulations (e. g. VDE0113, EN 60204)!

Observe when using the external switch-on current limitation E82ZJ004:
With

cyclic

mains switching, wait at least 3 minutes before your switch-on

the unit again. Otherwise, the external switch-on current limitation has no
effect.

STOP

Diagram

X1

motec 1

motec 2

X1

L2/N

L2/N

L2/N

L2/N

L2/N

L2/N

BR2

BR2

K14

K14

BR1

BR1

K12

K12

K11

K11

1/N/PE AC 180 V … 264 V

L1

L1

L3

L3

L1

L1

L2/N

L2/N

L1

L1

L3

L3

L3

L3

L1

L1

L1

L2

L3

N

PE

F1

K10

EDK82ZWKN2

00468456

06/03

Show/Hide Bookmarks

Advertising