PC system bus adapter 2173 / 2177

L

9

PC system bus adapter EN 1.1

5.3.1

Configuration of PC system bus adapter 2173

The following communication parameters have to be set for PC system bus adapter 2173:

Parameter

Presetting

Meaning

Baud rate

500 kbit/s

System bus (CAN) baud rate selected in the target system.

Lenze controllers are default set to 500 kbit/s.

I/O address

0x378h (LPT1)

Base address of the parallel interface (LPT port).

LPT port1: Address 0x378h

LPT port2: Address 0x278h

Interrupt

7 (LPT1)

Interrupt (IRQ) for the parallel interface (LPT port).

Time limit for

finding the bus

participants

1000 ms

Time during which the bus participants are expected to react when

identifying the bus participants connected to the system bus.

Communication

timeout

800 ms

Time after which an attempt to communicate with a bus participant will

be aborted.

Parameter

channel

2

Parameter channel for data transfer via the system bus.

Lenze controllers have 2 parameter channels

(SDO1 & SDO2).

Repeat

attempts

1

Number of communication attempts repeated when an error occurred.

Setting range: 1 ... 10

The standard settings for the LPT1 port and the default baud rate setting for Lenze controllers
are preset.

If you want to use an interface different from LPT1 for the system bus adapter or if the settings

for I/O address and/or interrupt differ from the standard settings, follow the instructions given in
chapter 5.3.1.2 to find out about the actual settings.

(

^

10)

Please make sure that the operating mode ”ECP” (Extended Capability Port) is selected for the

parallel interface in the PC BIOS.

5.3.1.1

Interrupt assignment to the LPT port

Only required for Windows 2000/XP!

Under Windows 2000/XP there is no standard interrupt assignment to the parallel interface.
Proceed as follows to assign an interrupt to the parallel interface under Windows 2000/XP:
1. Select

Settings

W

Control panel to open the control panel.

2. Double-click the entry

System to open the system properties.

3. Select the register

Hardware and press Controller manager.

4. Select the parallel interface (LPT port) and press the button

Properties.

5. Go to the register

Connection settings, choose ”Use every interrupt assigned to the

connection” as resource method and select the parallel interface under

LPT connection

number.