background image

ULDWB82T572

ASSEMBLY

INSTALLATION SHEET #IS-ULD

ULD Series 8" Speaker Assemblies

for Fire Protective Signaling

ULDSG82T572

ASSEMBLY

ULXCP84S ENCLOSURE

ULCP84 ENCLOSURE

ULP68X ENCLOSURE

ULCB84SG ENCLOSURE

Printed in U.S.A. 2-12-10

Lowell Manufacturing Company

100 Integram Drive

Pacific, Missouri 63069 U.S.A.

Call: 800-325-9660

Fax: 636-257-6606

Click: www.lowellmfg.com

ELECTRICAL AND AUDIBLE RATINGS

MAXIMUM

VOLTAGE

25 V

RMS

70.7 V

RMS

TLM572 (#13456)

TRANSFORMER TAP

5.0 W.

2.0 W.

1.0 W.

0.5 W.

0.25 W.

0.25 W.

0.5 W.

1.0 W.

2.0 W.

5.0 W.

ULDWB82T572

ULDSG82T572

88.8

ELECTRICAL SPECIFICATIONS

Frequency Response: 100Hz - 12kHz + 20dB

Intended Use: Indoor Dry Locations

8C10DVC Driver Size: 8"

8C10DVC Driver Power Rating: 15 watts RMS

Supervision Capacitor: 10uF 160V. Maximum Allowable Supervision Voltage: 100 VDC.

8C10DVC Magnet: 10 oz. Ceramic

8C10DVC Impedance: 8 Ohms

2kHz Dispersion at -6dB down points: With SG8 Grille:100 Degrees With WB8 Grille:100 Degrees

8C10DVC Driver Construction: Dual Paper Cone, Dual 1" Voice Coils, 20 Ga.Stamped Steel Basket

UL dBA RATING AT 10FT.

UL dBA RATING AT 10FT.

85.2

82.4

79.6

76.4

88.5

85.1

82.3

79.5

76.2

88.8

85.2

82.4

79.6

76.4

88.5

85.1

82.3

79.5

76.2

FRONT VIEW

70V-5W

70V-2W

25V-0.25W

70V-1W

25V-5W

25V-2W

25V-1W

REAR VIEW

25V-0.5W

70V-0.5W

70V-0.25W

70/25V COM

8 OHM

SPKR COM

FIGURE 1

#13456

TRANSFORMER TAPS

Note: The UL dBA ratings given above are the low readings from 11 samples so they may not be as expected for one sample.

Directional Characteristics Test With Full Power Pink Noise Input Measured at 3m:
On Axis = 91.1dBA, -3dBA at 25

o

off axis, -6dBA at 55

o

degrees off axis, 84.1dBA at 90

o

off axis

Installation - Series ULD (28LO) Fire Protective Signaling Speaker

These speakers are intended to be employed in either of the following configurations:

A. For fire alarm signaling service in conjunction with a compatible Listed system control unit, the
combination of which is intended to be installed as a combination system control in accordance
with the applicable requirements of NFPA 72 and the local authorities having jurisdiction. The
amplifier, in conjunction with the tone generator located in the control unit, provides the power and
signal, either for the alarm evacuation and/or for voice communication.

B. For general (non-fire alarm) signaling service in conjunction with compatible Listed sound
recording and reproducing equipment, the combination of which is intended to be installed in
accordance with the applicable requirements of the National Electrical Code and the local
authorities having jurisdiction. The amplifier or other sound reproducing equipment provides the
power for voice communication or any other related function to the speakers.

Connection Notes: For the supervised fire system voice coil, parallel input leads are provided
on Series ULD speakers for proper utilization of the electrical supervision scheme. Connect one
pair (red and black) to the incoming line from the fire alert signal source or previous speaker.
Connect the other pair (red and black) to the outgoing line to the next speaker or end-of-line
termination device. A red jumper is connected to the 70.7V 0.5W tap when shipped from the
factory. If desired, move the red jumper to a different transformer power tap lug. See "Figure 1"
on this page for available transformer power taps.

Instruction Sheet:
IS-ULD & IS-ULS

P/N 15741

Page 1 of 2

FIRE ALARM

EQUIPMENT

28LO

SIGNALING

LISTED

UL

R

Connection Notes: For the voice/music non-supervised voice coil, connect leads (white and
black) to the incoming line from the signal source or previous speaker. A red jumper is connected
to the 70.7V 0.5W tap when shipped from the factory. If desired, move the red jumper to a different
transformer power tap lug. See "Figure 1" this page for available transformer power taps.