SPECIFICATIONS

Platinum RTD Sensors:

±0.1% @ 32°F (0°C), Alpha: 385 per DIN 43760

Nickel RTD Sensors (#2):

±0.5°C @ 0°C (32°F), 5,000 PPM/K T.C.R.

Nickel RTD Sensors (#4):

±0.5°F @ 70°F (21.1°C), 6,000 PPM/K T.C.R.

Balco RTD Sensors:

±0.5°F @ 70°F (21.1°C), 4,300 PPM/K T.C.R.

Thermistor Sensors:

±0.2°C interchangeability @ 77°F (25°C)

Operating Temperature:

-40°F to 210°F (-40°C to 100°C)

Probe Material:

3/8" (9 mm) Bendable aluminum

Flange Material:

Galvanized Steel

Steel NEMA-1 (IP-30):

18 Ga. Galvanized Steel

Steel NEMA-4 (IP-65):

18 Ga. Cold Rolled Steel, Powder coated

Warranty:

Five Years (Lifetime on Moisture Migration)

EMC Conformance:

EN 55022, 55024, 61000-3-3,

61000-4-2, 3, 4, 5, 6 & 11

U.S. PATENT NO. 6592254, 7465087

For Additional Information See TE-705 Data Sheet

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

Model TE-705

Technical Information

TI.705-03

DUCT AVERAGING TEMPERATURE SENSORS

RoHS

ORDERING INFORMATION: TE-705-

INSTALLATION

TEMP SENSOR

PROBE

LENGTH

B Galvanized Steel

Enclosure

(NEMA-1 / IP-30)

C Painted Steel

Enclosure

(NEMA-4 / IP-65)

A 6 ft (1.8 m)

B 12 ft (3.6 m)

C 24 ft (7.2 m)

1 100-Ohm Platinum RTD
2 1,000-Ohm Nickel RTD

(5,000 PPM)

3 1,000-Ohm Platinum RTD

4 1,000-Ohm Nickel RTD

(6,000 PPM)

5 1,000-Ohm Balco RTD

7 10,000-Ohm NTC Thermistor

(Type III)

8 10,000-Ohm NTC Thermistor

(Carel)

10 3,000-Ohm NTC Thermistor
12 10,000-Ohm NTC Thermistor

(Type II)
13 5,000-Ohm NTC Thermistor

14 1,035-Ohm Silicon PTC
15 100,000-Ohm NTC Thermistor
16 10,000 ohm NTC Thermistor

..........

(Eliwell)

17 20,000-Ohm NTC Thermistor
18 2,252-Ohm NTC Thermistor
21 1,800-Ohm NTC Thermistor

Example: TE-705-B-10-B-1: Duct Averaging Temp Sensor, NEMA-1 enclosure,
12 ft. bendable 3/8" aluminum, 3,000 ohm NTC thermistor.

1 Bendable

3/8"

Aluminum

PROBE

TYPE

For Resistance vs. Temperature tables, please refer to TI.700-11.

Inspection

Requirements

INSTALLATION

Inspect the package for damage. If damaged, notify the

appropriate carrier immediately. If undamaged, open the

package and inspect the device for obvious damage.

Return damaged products.

Tools (not provided)

- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws

Appropriate accessories

Two #8 self-tapping mounting screws (not provided)

Training: Installer must be a qualified, experienced technician.

Advertising