Figure 16: Main Burner Flame

J.

Check thermostat operation. Raise and lower
temperature setting to start and stop boiler operation.

K.

Check ignition control module shut-off. Disconnect
igniter/sensor cable from Terminal 9 (SPARK). Gas
valve should close and pilot and main burners should
extinguish.

L.

Check low water cutoff (if used). Drain boiler water
below LWCO set point. Burners should extinguish.

M.

Check limit.

1. Adjust thermostat to highest setting.

2. Observe temperature gauge. When temperature is

indicated, adjust limit to setting below observed
temperature. Main burners and pilot burner should
extinguish and blower stop.

3. Adjust limit to setting above observed temperature.

Ignition sequence should begin.

4. Adjust thermostat to lowest setting. Adjust limit to

desired setting.

N.

Adjust gas input rate to boiler (Natural Gas).

1. Adjust thermostat to highest setting.

2. Check manifold gas pressure. Manifold pressure is

listed on rating label. Adjust gas valve pressure
regulator as necessary (turn adjustment screw
counterclockwise to decrease manifold pressure, or
clockwise to increase manifold pressure). If
pressure can not be attained, check gas valve inlet
pressure. If less than minimum gas supply pressure
listed on rating label, contact gas supplier for
assistance.

3. Clock gas meter for at least 30 seconds. Use Table 6

to determine gas flow rate in Cubic Feet per Hour.

4. Determine Input Rate. Multiply gas flow rate by gas

heating value.

5. Compare measured input rate to input rate listed on

rating label.

Seconds

for One

Revolution

Size of Gas Meter Dial

One-Half

Cu. Ft.

One

Cu. Ft.

Two

Cu. Ft.

30

60

120

240

32

56

113

225

34

53

106

212

36

50

100

200

38

47

95

189

40

45

90

180

42

43

86

172

44

41

82

164

46

39

78

157

48

37

75

150

50

36

72

144

52

35

69

138

54

33

67

133

56

32

64

129

58

31

62

124

60

30

60

120

Table 6: Gas Flow Rate in Cubic Feet per Hour

a. Boiler must not be overfired. Reduce input rate

by decreasing manifold pressure. Do not reduce
more than 0.3 inch w.c. If boiler is still
overfired, contact your Burnham distributor or
Regional Office for replacement Gas Orifice.

b. Increase input rate if less than 98% of rating

label input. Increase manifold gas pressure no
more than 0.3 inch w.c. If measured input rate is
still less than 98% of rated input:

i.

Remove Main Burners per procedure in
Section VIII: Service.

ii. Remove gas orifices. Drill one (1) drill size

larger (drill size is stamped on orifice, or
see Key No. 4D).

iii. Reinstall gas orifices and main burners.

Measure input rate.

6. Recheck Main Burner Flame.

7. Adjust thermostat to normal setting.

8. Return other gas-fired appliances to previous

conditions of use.

O.

Adjust gas input rate to boiler (LP/Propane).

1. Adjust thermostat to highest setting.

2. Check manifold pressure. Adjust gas valve pressure

regulator to obtain 10 inches w.c. manifold