Meltric PXN12c User Manual

Operating instructions, Warning

Advertising
background image

GENERAL

PXN12c/DXN25c/DXN37c plugs and receptacles

comply with international and European safety rules

and particularly with ATEX 94/9/CE Directive.

PXN12c/DXN25c/DXN37c products can be used in

zones 1, 2 (Gas), and 21, 22 (Dust).

There are inherent dangers

associated with electrical

products. Failure to follow safety precautions can

result in serious injury or death. These instructions

must be followed to ensure the safe and proper

installation, operation and maintenance of the Meltric

devices. Before installation, disconnect all sources of

power to the circuit to eliminate the risk of electrical

shock. It is imperative that Meltric explosion-proof

multicontact plugs and receptacles are connected or

disconnected without a load in a de-energized state.

INSTALLATION

PXN12c/DXN25c/DXN37c plugs and

receptacles must be used in conjunction with

other appropriately rated hazardous duty

products and must be installed by qualified

electricians in accordance with all applicable

local and national electrical codes.

Assembly

Optimum operating conditions are achieved by

installing PXN12c/DXN25c/DXN37c plugs and

receptacles with the latch at the top.

Wiring

Before starting, verify that the power is off, that

the product ratings are appropriate for the

application, and the conductors meet code

requirements and are within the capacities of

the terminals noted in Table 1.

The maximum cross-section of the conductors is

4934 CM (2.5 mm

2

) (solid or flexible). Conductors

must be stripped by .315 in (8 mm).

1. Contacts can be soldered or crimped. If

crimping, crimp the contact with a KNIPEX

crimping tool part # 61-CA500 or a GREENLEE

crimping tool part # 45505. Use the 4 mm

2

footprint whatever the conductor cross-section.

Perform a double crimping with a 90° rotation, in

compliance with IEN 60352-2.

2. Prior to soldering or crimping a heat shrink

sleeve (supplied- part # 9CP0250) must be

slipped over each conductor or alternatively an

insulating sleeve (supplied - part # 9SES201007301)

can be used but the insulating sleeve must be

installed using sleeve tool 61-CA500 (sold

separately).

3. If soldering use tin solder and a 50 W soldering

iron. Insert the conductor in the terminal and

heat the terminal for about 30 s. During heating,

insert the solder wire in the hole at the foot of the

terminal and let the solder penetrate by capillary

action. Let the terminal cool without any tension

on the conductor.

4. Slip the heat shrink or insulating sleeve over the

whole visible part of the contact, down to the molding.

5. Slide the heat-shrink sleeve up to the shoulder of

the contact. With a heat gun, apply heat evenly

370° around the sleeve until it shrinks around the

terminal and wire.

NOTICE: For a proper clamping, the use of PVC

cables is not recommended.

WARNING: This product must be electrically

grounded to Earth. A grounding terminal is provided

on all metal accessories.

Contact Assembly/Disassembly

Once wired, contacts must be inserted through the

rear of the interior moulding 1. Push each contact

fully home.  Check its proper engagement by a light

pull 2.  Contacts can be removed with the supplied

tool: insert the tool through the front 3 and push fully

home 4. Tool part # 9-LD12-37.

Contact Configurations

This is in reference to different keying positions on the

PXN12c. If or when 2 contacts are not in use, 9

different contact/keying configurations can be achieved

by plugging the contact holes not in use with the hole

plugs supplied.

OPERATION

To ensure safe and reliable operation, Meltric

plugs and receptacles must be used in

accordance with their assigned ratings.

Meltric plugs & receptacles can only be used in

conjunction with mating receptacles or plugs

manufactured by Meltric or another licensed producer

of products bearing the

TM

technology

trademark. WARNING: PXN12c/DXN25c/DXN37c

plugs and receptacles must be operated in

compliance with its explosion-proof classifications.

When not in use, the receptacle is shielded by a

protective lid preventing the entry of dust and

moisture.

This is held in the closed position by one or two

latch(es). To release the spring-loaded lid, depress

the latch(es).

DXN25c/DXN37c

To connect, align the plug bayonets with the hollow

part of the receptacle. Insert the plug and turn until

the stop. The plug is in the rest position, circuit is

open, figure 1. Push the plug fully home until

latched, figure 2. To disconnect, depress the latch.

The plug returns to its rest position, figure 3. Turn

the plug in the opposite direction to remove it. Shut

the receptacle lid, figure 4.

PXN12c

PXN12c

DXN25c

DXN37c

OPERATING INSTRUCTIONS

Meltric Corporation / 4640 Ironwood Drive Franklin, WI 53132
Tel. : 800 433 7642 / Fax : 414 817 6161 / e-mail : [email protected]

INSPXNDXNMULTI E

A manufacturer of products using Marechal technology

meltric

.com

WARNING

Table 1 — Wiring Terminal Capacity* (in AWG)

Contacts

Device

Min

Max

DXN25c

16

14

DXN37c

16

14

PXN12c

16

14

1

2

3

4

5

Contact

Tool

Advertising
This manual is related to the following products: