PAGE 36 — AP6/AP8 SERIES TRASH PUMPS • OPERATION AND PARTS MANUAL — REV. #0 (06/11/14)

Duration of Start By Frequency Parameter

The MSS-200 will disengage the starter motor when the

engine has reached a certain programmed frequency via

the frequency terminal of the alternator or proximity switch

(PNP).
This feature not only disengages the starter motor, but it

is also used as a safety feature by preventing the engine

from starting when the controller senses RPM.
Considering that a starter motor typically disengages at 500

RPM, use the following calculation below using an engine

with a 6 pole pair alternator and a belt ratio of 2:X where:

Pump Overspeed Shutdown (Course) Parameter

1. Parameters 20, 22, and 24 provide overspeed

shutdown for variable speed pump applications.

2. For parameter 20 select the next smaller number

calculated. In our example we calculated 360 Hz. The

next smaller number on the programming table is

240 Hz. Press the AUTO button until the LED pattern

matches the

240 Hz value.

Pressing the

OFF/SET button (Figure 26) saves the

programmed value and moves you to parameter 22.

Figure 26. SET Button (Saving Data)

6 x 500 x 2

=

60 Seconds

6000

60

=

100 Hz

=

X

6 x 1800 x 2

=

60 Seconds

21600

60

=

360 Hz

=

X

EXAMPLE: 1800 RPM Engine Engagement

PRESS TO SAVE VALUE

OPERATION (AUTO MODE)

Pump Overspeed Shutdown (Medium) Parameter

Subtract the frequency value entered in step 2 from the

total frequency calculated from step 1.

3. Divide the balance by the multiplier 16. Since you can

not use a fraction use the next smaller number (7) and

multiply by the multiplier (16) which in this example is

112 Hz. With this example, select the LED pattern that

matches

112 Hz.

Pump Overspeed Shutdown (Fine) Parameter

4. Subtract 360 Hz from the total sums entered in steps 1

and 2. The multiplier for step 3 equals 1 Hz. Parameter

24 would be programmed to 8 Hz.

Variable Speed Pump Mode Selection Parameter

1. Entering a value greater than zero programs the MSS-

200 controller to a constant engine speed mode. The

frequency programmed in parameter 26 then becomes

the overspeed shutdown frequency.
Should the engine speed mode not require overspeed

protection, then parameter 26 should be programmed

to the highest overspeed frequency setting available

(150 Hz). Use the following 2000 RPM calculation

to program overspeed for a constant engine speed

application:

Subtract 360 (total Hz of G/S in step #20, 22 and 24)

from 400 Hz (Over-Speed Hz) 400 – 360 = 40 Hz.

The multiplier for parameter 26 equals 10. Press the

AUTO or MAN buttons until the LED pattern matches

the 40 Hz value.

EXAMPLE: 360-240 = 120 (Balance)

120

16

= 7.5

7.5

7x16 = 112 Hz

240 Hz + 112 Hz = 352 Hz

360 Hz - 352 Hz =

8 Hz

EXAMPLE: Calculating Overspeed (Hz)

6 x 2000 x 2

=

60 Seconds

24000

60

=

400 Hz