Wiring – BKI FH-28 User Manual

Page 18

Advertising
background image

Ventless Hood System

Installation

16

3. If required, connect the provided fire extinguishing system contacts for remote signaling (refer to

the electrical diagram in this manual).

4. Adjust the position of the two ADP appliance nozzles as depicted below.

5. Reset control head. With control head NOT connected to cylinder, dry test system by activating

the remote pull.

6. Install cylinder by placing bottom of cylinder over socket head screws at the bottom of cylinder

bracket. Tighten pipe union located in the discharge line. Secure cylinder with adjustable
clamping strap.

7. Reset control head and connect control to cylinder.

8. Recheck installation procedure to insure that nothing has been overlooked.

Wiring

Electrocution, equipment failure or property damage could result if an unlicensed
electrician performs the electrical installation. Ensure that a licensed electrician
perform the electrical installation.

In the event of an appliance fire, serious injury, property damage or death could
occur if the appliance is powered from a source other than the hood. The cooking
appliance used under this hood MUST receive its input power from the hood. In
the event of a fire, the hood fire extinguishing system will automatically remove
power from the connected appliance.

Advertising