Paxton Net2 RS232/485 converter User Manual

Paxton, What data cable should be used? wiring

Advertising
background image

What data cable should be used?

Wiring

The converter is connected to the PC port with the supplied data cable.

CAT5 or Belden 8723

Reader

RS232/485

converter

Control

unit

USB

desktop

reader

White/Green

Green

White/Or

ange

Or

ange

12V

0V

12V DC

power supply

230V AC

input

Serial cable to PC

serial port

12V output. Total load including

converter should not exceed 1A

IMPORTANT: THIS IS NOT AN INPUT

Resistor x 2

1,000 metres max

02/02/2010

ALL OTHER SPARE

CORES

Resistor x 2

USB: This unit should NOT be

used with USB serial ports, as

they do not provide reliable

communication at the high

speed required by Net2.

END OF LINE TERMINATION - 120 ohm resistors must be linked across each data pair at the beginning AND end of the data

line. This can be done on many units with a switch or jumpers. If not, free resistors are provided with the converter. If the data

converter is located at a point along the data line, termination will then be required in the two ACU’s at each end of the line.

This product is not suitable for

retail sale. All warranties are

invalid if this product is not

installed by a competent person.

Ins-30055 Net2 RS232/485 converter

Technical Support

Technical help is available: Monday - Friday from 07:00 - 19:00 (GMT)

Saturday from 09:00 - 13:00 (GMT)

01273 811011

[email protected]

Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/

Paxton