Ins-30065 - RS485 protection module

Net2 data line protection

Under severe electrical storm conditions, the Net2 ACU's connected to the RS485 data line can be

damaged due to the very high induced voltages that can be present.

The best method of protecting the system is to make use of Fibre Optic or Wireless Networks between

outdoor locations or within large roof spaces. These then communicate with the Net2 PC over a LAN

network using a Paxton TCP/IP converter.

Where this is not practical, the fitting of surge suppressors to limit the voltage passing down the data

cable to 5V DC (RS485 standard) is strongly advised.

17/11/2011

This module is designed to suppress high voltage transients that can damage the communications

circuits of the Net2 ACU through its data line connection.

It makes use of TRANSILTM diodes that have an instantaneous response (less than 10 picoseconds) to

any overvoltage condition and will limit the voltage to a maximum to 5V DC with reference to the 0V

screen. Under extreme conditions, the diode will fail as a short circuit to 0V. The unit will then need to

be replaced before data transmission can be resumed.

Units should be placed at either end of any vulnerable cabling run to isolate the section.

Where to fit the modules

Protection Module

Red 12v dc

Br

own

Orange

Gr

een

Yellow

Blue

Mauve

Black/White

Br

own

Yellow

Reader 1

Orange

Keypad 1

+12v

0v

N.C.

N.O.

Com

N.C.

N.O.

Com

Alarm Output

0v

Contact

0v

Exit

0v

Tamper

PSU

Rx

Tx

Relay 1

Relay 2

Exit

Contact

Tamper

PSU

OK

5v

12v

Red

Brown

Orange

Green

Yellow

Blue

Mauve

Black/White

Brown

Yellow

Orange

Reader 2

Keypad 2

Power

Relay 1

Relay 2

Inputs

Network

CAT5 cable coding

White/Gr

een

Gr

een

White/Orange

Orange

1

2

3

4

Scr

een or spar

e cor

es

fr

om network cable

CAUTION: for 12v d.c. readers only

. For

correct connection of old 5v r

eaders, refer to

instructions.

Serial number

241821

Test ID: 012345678901

z-1440

3

2 4 8 9 8 0 0 0 0 0

4

Red 12v dc

Br

own

Orange

Gr

een

Yellow

Blue

Mauve

Black/White

Br

own

Yellow

Reader 1

Orange

Keypad 1

+12v

0v

N.C.

N.O.

Com

N.C.

N.O.

Com

Alarm Output

0v

Contact

0v

Exit

0v

Tamper

PSU

Rx

Tx

Relay 1

Relay 2

Exit

Contact

Tamper

PSU

OK

5v

12v

Red

Brown

Orange

Green

Yellow

Blue

Mauve

Black/White

Brown

Yellow

Orange

Reader 2

Keypad 2

Power

Relay 1

Relay 2

Inputs

Network

CAT5 cable coding

White/Gr

een

Gr

een

White/Orange

Orange

1

2

3

4

Scr

een or spar

e cor

es

fr

om network cable

CAUTION: for 12v d.c. readers only

. For

correct connection of old 5v r

eaders, refer to

instructions.

Serial number

241821

Test ID: 012345678901

z-1440

3

2 4 8 9 8 0 0 0 0 0

4

Red 12v dc

Br

own

Orange

Gr

een

Yellow

Blue

Mauve

Black/White

Br

own

Yellow

Reader 1

Orange

Keypad 1

+12v

0v

N.C.

N.O.

Com

N.C.

N.O.

Com

Alarm Output

0v

Contact

0v

Exit

0v

Tamper

PSU

Rx

Tx

Relay 1

Relay 2

Exit

Contact

Tamper

PSU

OK

5v

12v

Red

Brown

Orange

Green

Yellow

Blue

Mauve

Black/White

Brown

Yellow

Orange

Reader 2

Keypad 2

Power

Relay 1

Relay 2

Inputs

Network

CAT5 cable coding

White/Gr

een

Gr

een

White/Orange

Orange

1

2

3

4

Scr

een or spar

e cor

es

fr

om network cable

CAUTION: for 12v d.c. readers only

. For

correct connection of old 5v r

eaders, refer to

instructions.

Serial number

241821

Test ID: 012345678901

z-1440

3

2 4 8 9 8 0 0 0 0 0

4

Vulnerable Area

Protection Module

Technical Support