Paxton Net2 RS485 high speed repeater User Manual

Paxton, Pc acu, Technical support

Advertising
background image

Ins-30069 Net2 RS485 high speed repeater

27/06/2011

Technical Support

Technical help is available: Monday - Friday from 07:00 - 19:00 (GMT)

Saturday from 09:00 - 13:00 (GMT)

01273 811011

[email protected]

Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/

The 1 Km Rule

The Net2 data line uses RS485 data signalling. This specifies that the data line is connected to the units as a series

of point-to-point nodes, NOT as a star, ring or multiple line network. Each cable must be terminated at each end

and the total length of any single line must not exceed 1000 metres.

Without termination, reflections of these fast signals will cause data propagation (multiple signals) resulting in

some data corruption. Star and ring layouts do not allow correct termination and so are not allowed because of

these signal reflections.

Termination

No individual data cable can be longer than 1000 metres as this is limited by the power of the data converter. By

using a repeater we can originate another 1000 metre data line from any point. For example, if we require a data

line of 1500 metres, the repeater can be placed anywhere within 1000 metres of either end of the data line.

The two sections become individual data lines and therefore both must be terminated at each end.

This is done on many units with a switch or jumpers. If not, free resistors are provided with the data converter.

A
B
C
D

SCRN

A

B

C

D

SCRN

Orange

White/Orange

Green
White/Green
ALL OTHER SPARE CORES

ALL OTHER SPARE CORES

White/Green

Green

White/Orange

Orange

Termination

resistors

12v

0v

Existing network

Additional network

Red 12v dc

Brown

Orange

Green

Yellow

Blue

Mauve

Black/White

Brown

Yellow

Reader 1

Orange

Keypad 1

+12v

0v

N.C.

N.O.

Com

N.C.

N.O.

Com

Alarm Output

0v

Contact

0v

Exit

0v

Tamper

PSU

Rx

Tx

Relay 1

Relay 2

Exit

Contact

Tamper

PSU

OK

5v

12v

Red

Br

own

Orange

Gr

een

Yellow

Blue

Mauve

Black/White

Br

own

Yellow

Orange

Reader 2

Keypad 2

Power

Relay 1

Relay 2

Inputs

Network

CA
T5 cable coding

White/Green

Green

White/Orange

Orange

1

2

3

4

Screen or spare cores

from network cable

CAUTION: for 12v d.c. r

eaders only

. For

corr

ect connection of old 5v r

eaders, r

efer to

instructions.

Serial number

241821

Test ID: 012345678901

z-1440

3

2

4

8

9

8

0

0

0

0

0

4

Up to 5 repeaters can be used on a data network. This gives a maximum distance of 6000 metres for a data line

with a repeater placed every 1000 metres down the line.

The repeater 'direction' must be wired as above.

Although the repeater is a bi-directional unit, the LED indications will be incorrect if this is not done.

Mark 2 PCB: Red = 12V (always on); Green = PC data (flashes if data is received from PC direction);

Yellow = ACU data (flashes if data is received from ACU direction - ACU's are responding to the PC data)

Mark 1 PCB: Green = 12V (always on); Red = PC data (flashes if data is received from PC direction);

Yellow = ACU data (flashes if data is received from ACU direction - ACU's are responding to the PC data)

See also:

AN1087 - How to create multiple data lines and side spurs with a repeater. < http://paxton.info/876 >

This unit has onboard resistors which can be put into circuit by putting the jumper across the 2 pins.

A
B
C
D

SCRN

A

B

C

D

SCRN

Termination

Resistor jumpers fitted

Termination

Greater than 1000 metres

PC

ACU

Paxton