Prescolite 37CF-1, 4 User Manual

Instruction sheet, Installation instructions 37cf-1 and 4

Advertising
background image

Instruction

Sheet

www

.prescolite.com

• Prescolite

TollFree

Technical Support

1.888.PRS.4TEC

• Hours: 8am - 5pm ET

101 Corporate Drive • Spartanburg, SC 29303

With representatives offices in principal cities throughout North America.

Copyright 2005, 08/05 revision, All Rights Reserved - Printed in U.S.A.

Part No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .03424400

Instruction

Sheet

INSTALLATION INSTRUCTIONS

37CF-1 and 4

1.

Install the housing by nailing the mounting brackets on the

housing to the frame support as shown in Fig. 1, or frame in

the housing as desired for wet or dry wall construction.

2. Assemble the gasket and trim ring to the housing with (4) 6-32

x 1/4 flat head screws (provided in packet) as shown in Fig. 3.

Adjust the mounting brackets to locate the housing as required

for flush or profile trim (Fig. 2).

3. Install the conduit (by others) to align with the 1/2-14 NPT

tapped holes in housing as shown in Fig. 2. For through

wiring: align with hole to be used in J-Box (Fig. 4). Remove the

4 screws retaining the socket mounting plate and lift out plate.

For through wiring: remove the J-Box cover (Fig. 4).

4. When installed in concrete pour or mortar and in a situation

where direct water exposure is frequent, the concrete or mor-

tar is to be suitably treated with a sealing or repelling agent

to insure that the fixture housing does not retain continuously

wet.

5. Make electrical connections. Connect ground wires to green

ground leads. Connect white (common) to white leads.

Connect power supply (line) to black leads. (see wiring

diagram)
WARNING: DO NOT pinch wires. Consult a Qualified

Electrician for all other options that require other wiring

configurations. For through wiring: replace the J-Box cover

(Fig. 4). Replace the socket mounting plate and install lamp.

Support Frame

(By Others)

Housing Installation

Figure 1

Conduit

(By Others)

Housing

Ground Screw

IMPORTANT: When installed in brick or brick veneered

walls, the recessed portion of the housing must be coated

with asphaltum or similar protective material. Some types

of bricks retain moisture and other substances that can

damage the housing. Do not clean brick wall with acids

while fixture is in place.

Profile or Flush Trim

Figure 2

Adjustable Mounting

Bracket (2)

Fastener (Nail)

(By Others)

Flush Trim

(Wet Construction)

Adjustable

Mounting

Bracket (2)

Conduit

Entry

Profile Trim

(Wet or Drywall

Construction)

Housing

IMPORTANT SAFETY INFORMATION. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. Follow label information

and instructions concerning Wet or Damp Locations, installation near combustible materials, insulation, building materials,

and proper lamping. Do not install in areas subject to combustible vapors or gases. Before wiring to power supply and

during servicing or relamping, turn off power at fuse or circuit breaker. All servicing or relamping must be performed by

qualified service personnel. Product must be grounded to avoid potential electric shock or other potential hazard.

Product must be mounted in locations and at heights and in a manner consistent with its intended use, and in

compliance with the National Electrical Code and local codes. The use of accessory equipment not recommended by

the manufacturer or installed contrary to instructions may cause an unsafe condition. Do not block light emanating from

product in whole or part, as this may cause an unsafe condition. Do not allow items such as drapes, curtains, screens or

the like to come into contact with the product or to block light from the product, as this may cause an unsafe condition.

Advertising