Prescolite ARCHITRAK SYSTEM AKTEF - Live End Feed User Manual

Instruction sheet, Installation instructions architrak, System

Advertising
background image

Instruction

Sheet

www

.prescolite.com

• Prescolite

TollFree

Technical Support

1.888.PRS.4TEC

• Hours: 8am - 5pm ET

101 Corporate Drive • Spartanburg, SC 29303

With representatives offices in principal cities throughout North America.

Copyright 2005, 08/05 revision, All Rights Reserved - Printed in U.S.A.

Part No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157780100

Instruction

Sheet

INSTALLATION INSTRUCTIONS

FOR AKTEF LIVE END FEED.

FOR USE WITH PRESCOLITE AKT ONE/TWO CIRCUIT TRACK SYSTEM ONLY.

READ INSTALLATION INSTRUCTIONS BEFORE INSTALLING THE TRACK SYSTEM

SAVE INSTRUCTIONS FOR REFERENCE WHEN MAKING ADDITIONS TO OR CHANGES

IN THE TRACK SYSTEM CONFIGURATION.

INSTALLATION

1. Refer to PRESCOLITE AKT series track for track installation instructions

2. Loosen retaining screw at ends of connector.

3. Remove plastic cover from feed connector. Remove 7/8 Dia. Ko.

4. Align live end feed with pre-mounted track rail. Insert and press together.

5. For supply wire connection use approved 1/2” conduit connector.

6. For single circuit operation connect black wire (HOT) to brass terminal L-1. Connect white wire (NEUTRAL) to nickel

terminal N-1. Connect ground wire to green ground screw. For two wire circuits see wiring diagrams below.

7. Replace plastic cover.

L-2

GREEN GROUND SCREW

N-1

IMPORTANT SAFETY INFORMATION. READ AND FOLLOW ALL SAFETY INSTRUCTIONS. Follow label information

and instructions concerning Wet or Damp Locations, installation near combustible materials, insulation, building materials,

and proper lamping. Do not install in areas subject to combustible vapors or gases. Before wiring to power supply and

during servicing or relamping, turn off power at fuse or circuit breaker. All servicing or relamping must be performed by

qualified service personnel. Product must be grounded to avoid potential electric shock or other potential hazard.

Product must be mounted in locations and at heights and in a manner consistent with its intended use, and in

compliance with the National Electrical Code and local codes. The use of accessory equipment not recommended by

the manufacturer or installed contrary to instructions may cause an unsafe condition. Do not block light emanating from

product in whole or part, as this may cause an unsafe condition. Do not allow items such as drapes, curtains, screens or

the like to come into contact with the product or to block light from the product, as this may cause an unsafe condition.

INSTALLATION INSTRUCTIONS

ARCHITRAK

®

SYSTEM

N-1

L-1

L-2

RETAINING SCREW

N-2

L-1

N-2

WHEN WIRED IN THIS

CONFIGURATION ONE

SET OF BUSS BARS

WILL NOT BE ENERGIZED

L-1

BLACK (HOT) WIRE

WHITE (NEUTRAL) WIRE

GREEN GROUND SCREW

N-1

WIRE DIAGRAM 1-CIRCUIT

WIRE HOT WIRE TO L-1

NEUTRAL TO N-1, CONNECT

GROUND WIRE TO GROUND

SCREW..

WIRE DIAGRAM 1-CIRCUIT

WIRED FOR 2-CIRCUITS.

WIRE HOT WIRE TO L-1,

NEUTRAL TO N-1. BLACK

JUMPER WIRE TO L-1 AND

L-2, WHITE JUMPER WIRE

TO N-1 AND N-2. CONNECT

GROUND WIRE TO GROUND

SCREW.

WIRE DIAGRAM 2-CIRCUITS

CIRCUIT 1 WIRE HOT WIRE

TO L-1 NEUTRAL WIRE TO N-1

GROUND WIRE TO GROUND

TERMINAL.

CIRCUIT 2 WIRE HOT WIRE

TO L-2 NEUTRAL WIRE TO N-2

GROUND WIRE TO GROUND

TERMINAL.

NOTE: L-1, L-2 BRASS COLORED TERMINAL

N-1, N-2 NICKEL COLORED TERMINAL

JUMPER WIRES USE 12 GA.

STRANGED, UL/CSA LISTED

90 DEGREE WIRE.

Advertising