Specifications, Storage, Troubleshooting – Belkin F6C525 User Manual

Page 8

Advertising
background image

15

MODEL F6C325

F6C425

F6C525

F6C625

Specifications

Capacity 325VA

425VA

525VA

625VA

Voltage

100V, 110V, 120V, ±25%

Frequency

50Hz or 60Hz ±5% (auto sensing)

Voltage

Simulated sine wave at Line Input ±5%

(on battery)
Frequency

50Hz or 60Hz ±0.5%

(on battery)
Voltage

AVR automatically increases output voltage

Regulation

15% above input voltage if -9% to -25% of

AVR

nominal. AVR decreases output voltage
13% below input voltage if +9% to
25% of nominal

Transfer Time

2-4 milliseconds, including detection time

Spike Protection

320 Joules, 2ms

EMI/RFI filter

10dB at 15MHz,
50dB at 30MHz

Overload

UPS automatic shutdown if overload

Protection

exceeds 110% of nominal at 60 second
and 130% at 3 seconds

Unit Input

Fuse for overload and short circuit protection

10Base-T

Network (UTP, RJ45) compatible jacks

Cable Port

(F6C425, F6C525, F6C625)

Short Circuit

UPS output cut off immediately or input
fuse protection

Type

Sealed, maintenance-free lead acid

Typical

4 hours (to 90% of full capacity)

Recharge Time
Protection

Automatic self-test and discharge protection,
replace battery indicator

Back up Time

Depending on computer load...
5-17 min.

5-24 min.

5-32 min.

5-41 min.

Net Weight

4.7(10.4)

5.8(12.8)

6.2(13.7)

6.5(14.3)

Kg(lbs)
Shipping Weight

5.0(11.0)

6.1(13.4)

6.5(14.3)

6.9(15.2)

Kg(lbs)
Dimension(mm) 97

x

260

x

135

97x320x135

WxDxH
Input Inlet

IEC 320 power inlet

Battery

Slow beeping sound (about 0.47Hz)

Back-Up
Battery Low

Rapid beeping sound (about 1.824Hz)

Overload

Continuous beeping sound

RS232

Bi-directional communication port

Interface

(F6C425, F6C525, F6C625)

Safety

cUL, TUV, CE, meet FCC

Surge

Meet IEEE 587 standard

Ambient operation

6,000 meters max. elevation, 0-95% humidity
non-condensing, 0-48˚C

Audible noise

<40dBA (1 meter from surface)

Storage condition

15000 meters max. elevation

INPUT

OUTPUT

PROTECTION AND
FILTERING

BATTERY

PHYSICAL

ALARM

INTERFACE

CONFORMANCE

ENVIRONMENT

14

Storage

11.0 Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its
battery fully charged. Before storing, charge the UPS for at least 4
hours. Disconnect any cables connected to the computer interface
port to avoid unnecessary drainage of the battery.

11.1 Extended Storage

During extended storage in environments where the ambient
temperature is -15˚C to +30˚C (+5˚F to +86˚F), charge the UPS
battery every 6 months.

During extended storage in environments where the ambient
temperature is +30˚C to +45˚C (+86˚F to +113˚F), charge the UPS
battery every 3 months.

PROBLEM

POSSIBLE CAUSE

SOLUTION

Troubleshooting

On/off/test/ button not
pushed or pushed less
than 1 second

Battery voltage less than
10V

Load less than 20W
at battery mode

Power cord loose

AC fuse is burned out

Line voltage too high, too
low or black out

Battery not fully charged

Overload

Battery failure

The UPS continuously
beeps

Press the on/off/test button
more than 1 second

Recharge the UPS at least
4 hours

Normal condition

Replug the power cord

Replace the AC fuse

Normal condition

Recharge the UPS at
least 4 hours

Remove the
noncritical loads

Replace battery

UPS not on
LED not lit

UPS always at
battery mode

Back up time too short

RED LED lit