Chapter 4 Setup Menus

30

Code

Parameter

Unit

Range

A. PF.Ld

Low total PF Lead

0 to 1.000

Average Auxiliary Measurements
Ar neU.C

High neutral current

A

0 to Imax

Ar Hi.Fr

High frequency

Hz

0 to 100.00

Ar Lo.Fr

Low frequency

Hz

0 to 100.00

Present Demands
Hi d.U1

High volt demand L1

V

0 to Vmax

Hi d.U2

High volt demand L2

V

0 to Vmax

Hi d.U3

High volt demand L3

V

0 to Vmax

Hi d.C1

High ampere demand L1

A

0 to Imax

Hi d.C2

High ampere demand L2

A

0 to Imax

Hi d.C3

High ampere demand L3

A

0 to Imax

Hi d.P

High block interval kW demand

kW

0 to Pmax

Hi d.S

High block interval kVA demand

kVA

0 to Pmax

Hi Sd.P

High sliding window kW demand

kW

0 to Pmax

Hi Sd.S

High sliding window kVA demand

kVA

0 to Pmax

Hi Ad.P

High accumulated kW demand

kW

0 to Pmax

Hi Ad.S

High accumulated kVA demand

kVA

0 to Pmax

Hi Pd.P

High predicted sliding window kW demand kW

0 to Pmax

Hi Pd.S

High predicted sliding window kVA demand kVA

0 to Pmax

High Voltage Harmonic Distortions on any Phase
Hd03.U

High voltage harmonic H03

%

0 to 100.00

Hd05.U

High voltage harmonic H05

%

0 to 100.00

...

...

Hd39.U

High voltage harmonic H39

%

0 to 100.00

High Current Harmonic Distortions on any Phase
Hd03.C

High current harmonic H03

%

0 to 100.00

Hd05.C

High current harmonic H05

%

0 to 100.00

...

...

Hd39.C

High current harmonic H39

%

0 to 100.00

For parameter limits, see notes to Table 4-4.

The setpoint is operated when the actual phase sequence does not match the indicated

normal phase rotation.

The actual frequency range is 45.00 - 65.00 Hz.
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for

any other wiring mode, they will be line-to-line voltages.