Chapter 5 Setting Up the ETC2002

Configuring Data Server

ETC2002 Network Communicator

51

5. Check the “Auto Reset” box if you want the status register

to be cleared after polling.

Write Data Exchanges

To enter the Setup dialog, select the ETC2002 site from the list box on the
PAS toolbar, select ETC2002 Setup from the Meter Setup menu, and then

click on the Write Data Exchanges tab.

See

Data Server

in Chapter 3 for more information on using data exchanges.

Refer to the ETC2002 Modbus Guide for information on how to put data into
a write exchange and to trigger it via communications.

The following table lists available options.

Parameter Options

Default Description

Device address

1-247

1

Define the device to which
the exchange is linked

Device Start Register

0-65535

0

Defines the start device

register for a write

Block Size

1-12

0

Defines the number of
contiguous registers in the
write exchange

Write Enabled

Disabled,

Enabled

Disabled

Enables writing data to the

device upon a trigger

To configure a write data exchange:

1. Define the device address for a write data exchange. Note

that the real-time, status event and write data exchanges
with the same exchange number are internally linked in
the ETC2002 to the same device address.

2. Specify the start register address of the area in the device

Modbus map you wish to be written via the exchange.

3. Type the number of contiguous registers in the exchange.
4. Check the “Write Enabled” box to activate the exchange.

Advertising