5 Troubleshooting: Fault Condition Display

The RDM172 fault condition screen provides an indication of
communication problems, should any occur.

Reasons for a communication fault could be:

Instrument switched off

Communication cable disconnected

Instrument communication setup changed

RDM172 communication setup changed

Press to check or alter the RDM172 adjustment and scroll to
communication options.

6 Communications

NOTE

Where an RS-232/RS-422 converter is used, R1 is not applicable
since it is built in to the converter.

Use a shielded, 0.33 mm

2

/22 AWG twisted pair cable for each

communication link; terminate the ends of multi-drop line with 200-500
Ohm resistors. Connect the cable shield to the ground input.