Using the navigation buttons – SATEC RDM172 Quick Start-2 User Manual

Page 7

Advertising
background image

PM172 Quick Start Guide

Series PM172 Powermeters

7

The typical installation diagram above shows a 4-Wire Wye 2½-element

connection using 2 PTs and 3 CTs. The wiring mode is 3LL3 or 3Ln3. The voltages
must be balanced for the configuration to provide accurate power measurements.
There are approximately nine different wiring configurations in the PM17X Series.
Refer to the Installation and Operational Manual for additional configurations.
For electrical installation of the display panel follow the following steps:

1. Connect the remote display using the pinout tables below, either for a

self-powered display or a remote powered display. Refer to the

Installation and Operation Manual for the wiring schematic diagrams.

Pinout for a self-powered remote display

PM172
D15 Female
Pinout

Signal

Remote
Display
D15 Male
Pinout

1 +12V

1

5

RS-485 + (plus)

5

7

RS-485 - (minus)

7

8 GND

8

15 Chassis

15

Pinout for a remote display powered from an external 12V DC,

350 mA power source

PM172
D15 Female
Pinout

Signal

Remote
Display
D15 Male
Pinout

1 N.C.

+12V

1

5

RS-485 + (plus)

5

7

RS-485 - (minus)

7

8 N.C.

GND

8

15 Chassis

15

2. Connect the DC or AC power.
3. Connect the chassis ground.
4. Connect the required wiring configuration.
5. Connect the I/O connections as required. For I/O ratings, see the

Technical Specifications section in the Installation and Operation Manual.

Using the Navigation Buttons

Figure 9: Navigation Buttons