Schwank supraSchwank User Manual

Page 12

Advertising
background image

supra/primo Manual

IM091112

RD: APR 2013

RL: 13B

12

SUSPENDED HORIZONTALLY TO 30°:

TABLE 2: SUGGESTED LAYOUT MOUNTING DISTANCES FOR COMFORT*

MODEL

primoSchwank or

supraSchwank

TYPICAL ABOVE

FLOOR

< X >

TYPICAL BETWEEN

HEATERS

< Y >

TYPICAL

BETWEEN ROWS

< Z >

10
15
20
30

15' (460 cm)
18' (550 cm)
20' (610 cm)
24' (730 cm)

25' (760 cm)
30' (915 cm)
35' (1070 cm)
45' (1370 cm)

30' (915 cm)
40' (1220 cm)
50' (1525 cm)
70' (2135 cm)

FIGURE 3: SUGGESTED SPACING FOR COMFORT

* The Mounting distances are suggested, and may vary depending on insulation val-

ues, air movement / change, and other site conditions. If in doubt, please contact
Schwank Technical Services.

For ‘spot’ heating, the distance above the floor can be reduced by 2 to 4 feet (61 to

132 cm) depending upon site conditions.

** IMPORTANT: When angle mounted the gas-inlet/venturi side of the heater

MUST BE IN THE UPPER POSITION.

Y

X

X

Z

X

Z

SUSPENDED AT AN ANGLE** 30° TO 45°:

MODEL

primoSchwank or
supraSchwank

TYPICAL ABOVE

FLOOR

< X >

TYPICAL BETWEEN

HEATERS

< Y >

TYPICAL

BETWEEN ROWS

< Z >

10
15
20
30

13' (400 cm)
16' (490 cm)
18' (550 cm)
21' (640 cm)

25' (760 cm)
30' (915 cm)
35' (1070 cm)
45' (1370 cm)

50' (1525 cm)
75' (2290 cm)

100' (3050 cm)
140' (4270 cm)

Venturi
in upper
position

Long axis always level

Short axis may
rotate up to 30°

Advertising