Schwank compactSchwank P40-R User Manual

Page 17

Advertising
background image

17

P40R-F I&O Manual

IM120801

RD: MAY 2014

RL: 3A

For 30° angle mount: Install the tube system; Loosen 4 nuts holding burner to tube flange;
rotate burner to horizontal orientation; re-tighten 4 nuts. (see full instructions previous page)

Use all four suspension points plus a chain at the burner eye hook.
Hardware capable of supporting minimum 100 lbs (45 kg) at
each suspension point.
For seismic and high wind restraint see
Sections 10-A & 10-B.

FIGURE 5 TYPICAL SUSPENSION

72

(1

83

cm

)

SERVICE ACCESS: ALLOW A MINIMUM OF 6
INCHES (15 cm) FROM THE ACCESS END
OF THE BURNER AND A MINIMUM OF 24
INCHES (60 cm) FROM EITHER SIDE OF THE
BURNER TO A WALL OR ANY OBSTRUC-
TION THAT WOULD RESTRICT OR LIMIT
ACCESS TO THE BURNER (SEE SECTIONS
6 & 7 - PRE-INSTALLATION SURVEY AND
MOUNTING CLEARANCES)

Connect to properly
grounded 120V
power supply

FIGURE 6 HEATER DIMENSIONS & SUSPENSION ANGLE OPTIONS

Burner always

horizontal

Vent side

always upper

Turbulators (factory installed in tube): Burner side tube: 36” (91 cm)

Vent side tube: 90” (229 cm)