18. TROUBLESHOOTING GUIDE FOR SER / IR- 45 HONEYWELL S87J1034

SET THERMOSTAT TO CALL FOR HEAT

COMBUSTION AIR BLOWER STARTS

YES

NO

YES

NO

CHECK THERMOSTAT

CHECK FOR LINE VOLTAGE POWER SUPPLY

YES

NO

CHECK WIRING CONNECTION AND
REPLACE BLOWER MOTOR IF DEFECTIVE

AIR PROVING SWITCH CLOSED
24 VOLTS AT INGITION CONTROL

YES

NO

→ENSURE THAT THE AIR INTAKE AND FLUE ARE NOT
BLOCKED
→ENSURE PRESSURE TUBE IS CONNECTED AND NOT
BLOCKED
→CHECK AIR PRESSURE WITH MANOMETER
→CHECK AIR PROVING SWITCH IS CLOSING WHEN
BLOWER IS RUNNING
→REPLACE DEFECTIVE SWITCHES

SPARK ACROSS IGNITER OR
IGNITER/SENSOR GAP

YES

NO

→SEE APPENDIX 1 PAGE 24 SPARK IGNITION CIRCUIT
→PULL IGNITION LEAD AND CHECK SPARK
→CHECK SPARK GAP, ADJUST TO 3/16” IF REQUIRED
BY MOVING THE GROUND PRONG ONLY

→SPARK OK?

REPLACE IGNITION CONTROL

→CHECK IGNITION CABLE, GROUND WIRING
CERAMIC INSULATOR AND C A P, A N D
CORRECT
→CHECK BOOT OF THE IGNITION CABLE FOR
SIGNS OF MELTING OR BUCKLING
→TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE
TEMPERATURES