Peco nema 4x industrial controls technical data, Models, Wiring connections – Schwank White-Rogers 24 Volt Digital Thermostat User Manual

Page 2: Ratings, Two speed heating two speed cooling

Advertising
background image

Automation & Controls
Division of PECO, Inc.
Portland, OR 97282

800-874-8547

or

503-233-6401

[email protected]

www.pecomanufacturing.com

PECO

NEMA 4x Industrial Controls

Technical Data

Models

Model

Part No.

Temp. Range

Diff.

Dimensions

Switch Action

Bulb

TF115-001

68471

40° F to 110° F

Fixed 3 F

3.1" W x 6.5” H x 2.5" D

SPDT

Coiled Air - Stainless

TF115-023

70254

-30° F to 100° F

Fixed 6 F

3.1" W x 6.5” H x 2.5" D

SPDT

Coiled Air - Stainless

TRF115-005

68426

0° F to 120° F

Fixed 3 F

3.1" W x 6.5” H x 2.5" D

SPDT

5' Stainless Remote

TRF115-007

69320

-30° F to 100° F

Fixed 6 F

3.1" W x 6.5” H x 2.5" D

SPDT

8' Copper Remote

TH109-009

68427

40° F to 100° F

3°/ Stage

3.5" W x 7.3” H x 4.9" D

2- SPDT

Coiled Air - Stainless

T109

T115

TH109-009

VIOLET

BROWN

L1

BLUE

BLACK

L1

RED

PINK

HEATING LOAD

COOLING LOAD

L2 OR NEUTRAL

TEMP RISE

VIOLET

BROWN

L1

BLUE

BLACK

CAN BE TIED TO A LOUVER
OR CURTAIN CONTROL

RED

PINK

HIGH COOL

LOW COOL

L2 OR NEUTRAL

TEMP RISE

VIOLET

BROWN

L1

BLUE

BLACK

RED

PINK

HIGH HEAT

LOW HEAT

L2 OR NEUTRAL

TEMP RISE

VIOLET

BROWN

L1

BLUE

BLACK

L1

RED

PINK

FIRST STAGE COOL

SECOND STAGE COOL

L2 OR NEUTRAL

TEMP RISE

VIOLET

BROWN

L1

BLUE

BLACK

L1

RED

PINK

SECOND STAGE HEAT

FIRST STAGE HEAT

L2 OR NEUTRAL

TEMP RISE

Two Stage Cooling

Two Stage Heating

Auto Changeover Control

1 Heat/1 Cool with 3˚ F dead band

Two Speed Heating

Two Speed Cooling

Wiring Connections

TH109

TF115 & TRF115

3.1”

(78 mm)

5.0”

(128 mm)

6.4”

(162 mm)

2.5”

(64 mm)

3.5”

(88 mm)

7.0”

(178 mm)

7.3”

(186 mm)

4.9”

(125 mm)

Double pole, double
throw contacts
operate sequentially
with 3° F (1.7 C)

nominal separation on

temperature rise or fall.

DS-T109-T115 6/10

Gas

Electric

Fan

Refrigeration

TF115-001
TF115-023
TRF115-005
TRF115-007

Ratings

Voltage Rating

FLA

LR

Non-Inductive Pilot Duty

120 V

AC

16.0 A 80.0 A

25.0 A

125 VA

208 V

AC

13.2 A 66.0 A

25.0 A

125 VA

240 V

AC

12.0 A 60.0 A

25.0 A

125 VA

277 V

AC

10.0 A 50.0 A

22.0 A

125 VA

Suitable for 24 V

AC

operation

Advertising