P:\INSTALLATION INST\Power Supplies\INST-632RFA.vsd Rev A 04-13

POWER SUPPLY

INSTALLATION INSTRUCTIONS

MODEL 632RFA

801 Avenida Acaso, Camarillo, Ca. 93012

(805) 494-0622 • Fax: (805) 494-8861

www.sdcsecurity.com • E-mail: [email protected]

MAIN SYSTEM ON-OFF OR

FIRE PANEL CONNECTION

Min. Switch or

Contact Ratings

100mA @ 30VDC

POWER SUPPLY SPECIFICATIONS

Input Voltage: 115 VAC @ 60hz
Input Current: 1.0 amps Max.

Output Voltage: 12/24VDC
Output Voltage Ranges:

12 V Operation: 9.2 – 12.0 VDC
24 v Operation: 21.2 – 24.0 VDC

Output Current: 2.0 amps
Ripple Voltage: 0.05 Volts Max.

Battery Charger Max. Current: 0.25 amps
Maximum recommended battery size: 4ah
(Replace batteries every 3 years)

Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply

TEST UNIT ANNUALLY

BATTERY 1

4ah

POWER

SUPPLY

BOARD

BATTERY 1

4ah

COMPONENT LOCATIONS

STANDARD BOX

CONTROL
MODULE

CONTROL
MODULE

+

_

C

Master ON/OFF

Switch (N/C)

+

_

C

Fire Panel

Contact (N/C)

Note: Power limited

cable must maintain a

1/4” or more of spacing

from battery cables or

primary power wires.

7ah batteries require an

Auxiliary battery box

MODEL 632RFA

24V

12V

CHG FLOAT

AC

PRESENT

AC VOLTAGE

INPUT

VOLTAGE SELECT

SWITCHES

BATTERY CHARGER

STATUS

BATTERY INPUT

TERMINALS

MANUAL RESET

+

-

C

+

-

SYSTEM STATUS

YELLOW – SYSTEM OK

RED – ON BATTERY PWR
GREEN – NO DC OUTPUT

VOLTAGE OUTPUT

TERMINALS

12 Volt Mode Battery

Connections

12VDC

SET

SWITCH

FOR

12VDC

+

C

_

+

_

12VDC

SET

SWITCH

FOR

24VDC

+

C

_

+

_

12VDC

24 Volt Mode Battery

Connections

Power
Supply

Battery

+

C

_

HIGH

VOLTAGE

INPUT

POWER

LIMITED

CLASS 2

OUTPUT

+

_