P:\INSTALLATION INST\POWER SUPPLY\INST-ACM-1\INST-ACM-1.vsd REV B 04-12 Page 1

Any suggestions or comments to this instruction or

product are welcome. Please contact us through

our website or email [email protected]

ELECTRICAL DATA

12/24vdc Input Voltage.
75mA Input controller current.
3 – N/C Normally Closed Inputs with screw terminals.
3 – N/O Normally Open Inputs with screw terminals.
5 Amp (Resistive) Fail Safe Lock Output.
5 Amp (Resistive) Fail Secure Lock Output.
Lock Status Output – SPDT (Form C) Dry Contact.
Green LED Indicator – Illuminated when lock is activated.
Size: 3.20” (81.28mm) W x 2.00” (50.8mm) L x 1.00” (25.4mm) H.
Fits all SDC Power Supplies. Requires 1 Module space.
Supplied with mounting screws and standoffs for J-box mounting.

POWER

SUPPLY

POWER

+

-

+

-

COM

N/C

N/O

MONITOR

OUTPUTS

FAIL SAFE

LOCK

FAIL SECURE

LOCK

or

D3

RELAY ACTIVE

INDICATOR

N/O REX INPUTS

N/C REX INPUTS

NOTE:
JUMPER ALL
UNUSED N/C
INPUTS

N/C
ACCESS
CONTROL

N/O
ACCESS
CONTROL

ADD JUMPER FOR
12VDC OPERATION

The SDC ACM-1 Access Control Module is an
installer friendly interface relay board designed to
release a magnetic locking device or electric strike,
to provide a lock status output and to provide easy
to use multiple wiring terminals for additional access
control REX (Request to Exit) inputs.

Operation
When any REX input is activated, the relay will release the
magnetic lock or electric strike. The Lock Status Output will
change state and the green LED will illuminate.

Compatible with any Request to Exit (REX) output, i.e.
Request-to-Exit Push Bar, Keypad, Card Reader, Motion
Sensor, Push Button or Key Switch.

C NC C NC C NC C NO C NO C NO

ACTIVE

SECURITY DOOR CONTROLS

801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: [email protected]