Chapter 7: Wireless Sensors

37

WSg WiRELESS 4-20MA SENSoR

INTRODUCTION

The WSG Wireless 4-20mA sensor provides remote monitoring of

4-20mA transducers without running wires. Contact data is sent from the

sensor to the WSG30 via an integrated 2.4GHz Wireless radio. The device

can transmit its signal up to 300’ indoors and even greater distances when

it has line-of-site. The WSG30 series of Wireless sensors also feature mesh

networking technology, which allows each sensor to be used as either a

Wireless sensor/router or as a low-power battery operated sensor (also

referred to as an end point). When used as a router, greater distances can

be realized because each sensor/router adds another 300’ of range to the

system. The sensor comes with 3 AA alkaline batteries which will power

the sensor for up to 2 years (end point mode). An optional plug-in power

supply is also available, in which case the batteries function as backup

power if main AC power fails (power supply required for router mode).

NOTE: Do not install the sensor in a dirty, humid, or corrosive

environment . Do not install the sensor in close proximity to other 2 .4GHz devices (WiFi, etc) .

Do not install the device inside of a metallic enclosure as this will impede it’s ability to Wirelessly

communicate with the WSG30 .

PaCkage Contents
(1) Wireless 4-20mA Sensor

(3) AA Alkaline batteries

(1) 5VDC Power Supply

(1) Plastic drywall anchors

(1) #6 Metal tapping screws

InstallatIon suMMary
1) Locate the sensor serial number on the small white label inside the sensor enclosure .
2) Enter the serial number into the WSG30 using the web page or keypad.
3) Mount the sensor.
4) Attach power supply if using as a router and install the batteries.
5) Watch the LCD or web page to confirm that the sensor has connected with the WSG30.

sensor regIstratIon
Before you power-up the sensor you must enter the serial number, located on the small white label

inside the sensor enclosure, into the WSG30. You can do this with the WSG30 web page or you can

enter it using the WSG30 keypad (see Sensor Registration earlier in this manual). Just be sure to jot

down the serial number before you attach the sensor to the wall.

Battery InForMatIon
The Wireless 4-20mA Sensor can be used with or without the internal 24VDC supply. When the

internal supply is used to power the transducer the device must be powered by an external power

supply, in which case the batteries are used as a backup in the event of a power failure. In this scenario

the batteries will last approximately 15 hours.
When the 4-20mA sensor is used with the internal 24VDC supply disabled, you can operate it on

battery power only. The approximate battery life is 2 years at a sampling frequency of 3 seconds.