Warning, Caution – Burnham MST396 User Manual

Page 42

Advertising
background image

4

WARNING

Before installation of the boiler is considered

complete, the operation of all boiler controls must

be checked, particularly the primary control and

pressure limit control.

2. VERIFY PRIMARY CONTROL FEATURES

using procedures outlined in Instructions furnished

with control or instructions as follows:
a. FEATURES AND CONTROLS

i. The R7184 is a microprocessor-based

control. The indicator light provides

diagnostic information for lockout, recycling

and patented cad cell status. There is a

manual reset button to exit the Lockout

Mode and enter the Idle Mode (see Figure

25).

Figure 5: R184 Terminals, LED and Reset Button

ii. Pump Priming Cycle: To facilitate purging

air from the oil lines and filters, the R7184

can be placed in a purge routine by pressing

and releasing the reset button during the

safety check, delayed valve-on, ignition or

carry-over periods.

iii. Limited Recycle: This feature limits the

number of recycle trials (for each call

for heat) to a maximum of three trials. If

the flame is lost three times and does not

successfully satisfy a call for heat, the

R7184 locks out.

iv. Limited Reset (Restricted Mode): In order

to limit the accumulation of unburned oil in

the combustion area, the control can only be

reset three times. The reset count returns to

zero each time a call for heat is successfully

completed.

To reset from Restricted Mode: Press and

hold the reset button for 30 seconds.

When the LED flashes twice, the device

has reset.

v. T-T Jumper: Select models have pre-

installed T-T jumper. Do not remove

jumper. See Figure 25.

vi. Diagnostic LED: The indicator light on oil

primary control provides lockout, recycle

and cad cell indications as follows:

Flashing at 1 Hz (½ second on, ½ second

off): system is locked out or in Restricted

Mode.

Flashing at ¼ Hz (2 seconds on, 2 seconds

off): control is in Recycle Mode.

On: cad cell is sensing flame.

Off: cad cell is not sensing flame.

vii. Cad Cell Resistance Check: For proper

operation it is important that the cad cell

resistance is below 1600 ohms. During a

normal call for heat, once the control has

entered the Run Mode, press and release the

reset button. Indicator light will flash 1 to 4

flashes. See Table 7 for equivalent cad cell

resistance.

TABLE : CAD CELL RESISTANCE WHEN

SENSING FLAME

b. CHECK OIL PRIMARY CONTROL

CAUTION

Due to the potential hazard of line voltage,

only a trained, experienced service technician

should perform the following safety checks.
This control contains no field-serviceable

parts. Do not attempt to take it apart.

Replace entire control if operation is not as

described.

i. Preliminary Steps

Check wiring connections and power

supply.

Make sure power is on to the controls.

Make sure limit control is closed.

Check contacts between ignitor and the

electrodes.

Check the oil pump pressure.

Check the piping to the oil tank.

Check the oil nozzle, oil supply and oil

filter.

ii. Check Safety Features

Safe Start:

Flashes

Cad Cell Resistance in ohms

1

Less than 400

2

More than 400 and less than 800

3

More than 800 and less than 1600

4

More than 1600 and less than 5000