KPC Capacitor Bank

Installation Instruction

INPUT

When installing the KPC capacitor

bank on the INPUT side of the Variable

Frequency Drive (VFD) or induction

motor, please use the following guidelines

when wiring the unit:

The KPC capacitor bank is wired in

parallel with the load.

Refer to NEC wiring practices for

appropriate wire sizes for your application.

Power Wiring: Only use 75°C

copper conductors unless the wire

connector is marked for Al/Cu, then the

use of aluminum wire is permitted.

In standard 40°C ambient or less

installations, a clearance of 3 inches on

all sides of the capacitor bank and its

enclosure is recommended for assisting in

heat dissipation and ample wire bending

space.

These capacitors are designed to be

panel mounted.

Field Wiring Information

Below are typical wiring diagrams for

the 3-phase KPC applied to the Variable

Frequency Drive (VFD) or motor.

3-phase and 1-phase, 600 Volt Class

UL Listed; File E-116124

kVar rated device

Ambient Temperature: 40°C

Product Specifications

Wiring Diagram

Line

VFD or

Motor

A

B

C

Wiring Diagram with Tuning Reactor

Line

VFD or

Motor

A

B

C

If tuning

reactor

used

Optional Thermal Switch

Wiring: KPC has 3 power terminals, 1 for each

phase of 3 phase circuit. Wire in any order.

Up

to 40

Kvar

80

Kvar

180

Kvar

240

Kvar

300

Kvar

H (in.) for encl

17.4

28.0

52.0

70.0

72.0

W (in.) for encl

17.0

17.0

17.0

20.0

36.0

D (in.) for encl

12.3

12.3

16.3

20.0

24.0

Vent Area top (in2) 24.0

55.0

76.0

57.5

75.0

Vent Area bottom

(in2)

21.0

10.0

28.5

50.0

112.5

Required Minimum Dimensions

if product is enclosed: