Field Wiring

Field Wiring Connection Terminals

Compression type terminals are provided for all line

wiring connections. The wire size capacity ranges and

tightening torque for the power terminals are listed in the

table.

Warnings and Cautions

Dangerous Voltage Warning: warns of

situations in which a high voltage can

cause injury and/or equipment damage.

The text next to this symbol describes

ways to avoid danger.
General Warning: warns of situations

that can cause physical injury and/

or equipment damage by means other

than electrical. The text next to this

symbol describes ways to avoid the

danger.

General Safety Instructions

Be sure to read, understand, and follow

all safety instructions.

Only qualified electricians should

carry out all electrical installation and

maintenance work on V1k drive output

filters.

All wiring must be in accordance with

the National Electrical Code (NEC)

and/or any other codes that apply to

the installation site.

Disconnect all power before working

on the equipment. Do not attempt any

work on a powered V1k output filter.

The V1k, VFD, motor, and other

connected equipment must be properly

grounded.

The VFD terminals and connected

cables are at a dangerously high voltage

when power is applied to the VFD,

regardless of motor operation.

Warning

Warning

Warning

Warning

Warning

Warning

Warning

Warning

!

!

!

!

See www.transcoil.com for dimensions tables. Please contact

TCI Technical Support or your TCI distributor for application

information regarding the use of V1k output filters on the

output side of the VFD.

V1k Model

Numbers

Input and Output Motor Power

Wire Size

Torque

(in.-lb.)

V1k2A to V1k12A

12 - 14

10

V1k16A

4 - 12

20

V1k18A to V1k21A

4 - 10

20

V1k25A to V1k27A

4 - 8

20

V1k35A

6 - 8

30

V1k45A

6

30

V1k55A

1 - 4

35

V1k80A

1 - 3

35

V1k110A

2/0 - 1/0

50

V1k130A

2/0

50

V1k160A

250 MCM - 3/0

375

V1k200A

two 2/0 - 1

50

V1k250A

two 2/0

50

V1k305A

600 MCM,

two 500 MCM - 3/0

500

V1k362A

two 350 MCM - 4/0

375

V1k420A

two 600 MCM - 300

500

V1k480A

two 600 MCM - 350

500

V1k600A

two 600 MCM - 500 MCM

500

V1k750A

three 600 MCM - 400 MCM

500

All electrical connections must be

re-torqued annually.