BAC-8001 and BAC-8201 VAV Controllers

Installing the controllers

Mounting

10

Mounting

Mount the controller inside of a metal enclosure. To maintain RF emissions
specifications, use either shielded connecting cables or enclose all cables in
conduit.

Mount the controller directly over the damper shaft. A minimum shaft length of
2.0 inch (51 mm) is required.

Note

.

Mount the controller close enough to the pitot tubes to keep the tubing length to
a minimum. In typical installations the controller’s inputs and sensors are within
24 inches of each other.

Mount the controller as follows:

1. Loosen the nuts on the U-bolt until the shaft can fit through the collar.

2. Place the controller on the damper shaft in the approximate final position.

Position the controller loosely against the mounting surface so that the

mounting bushing can float freely in the mounting tab.

3. Center the mounting bushing in the slot of the mounting tab and secure it

using a #8 self-tapping screw.

4. Manually position the damper in the full open position.

5. Adjust the drive hub as follows:

a. If the damper rotates counter clockwise to close, depress the gear

disengagement button and rotate the drive hub to the full clockwise

position then release the button.

b. If the damper rotates clockwise to close, depress the gear disengagement

button and rotate the drive hub to the full counter clockwise position

then release the button.

6. Lock the hub to the shaft by evenly tightening the V-bolt nuts to 30 to 35

in-lbs.

Illustration 2-2 Controls and indicators

Mounting tab

Gear disengagement button

Airflow sensor inputs

Drive hub

and V-bolt

Status LEDs

Mounting bushing

The controller is designed to directly mount to 3/8 to 5/8 inch (9.5 to 16mm)

round or 3/8 to 7/16 (9.5 to 11mm) square damper shafts.