Dual Duct VAV Terminals

Receiving Inspection

After unpacking the terminal, check it for

shipping damage. If any shipping

damage is found, report it immediately

to the delivering carrier. Store units in a

clean, dry location prior to installation.

Caution: Do not use the flow sensor,

connecting tubing, or damper shaft

linkage as a handle to lift or move

assembly. Damage to the flow sensor

or controls may result.

Supporting the Assembly

Dual duct terminals are not light enough

to be supported by the duct work itself.

The terminal should be supported

directly. Straps screwed directly into the

side of the terminal, threaded rod

through the optional hanger brackets

(see Figure 1), or the method prescribed

for the rectangular duct on the job

specifications may be used. The bottom

should be left clear where there are

access panels.

Important: If equipped with pneumatic

controls, the terminal must be mounted

right side up. It must be level within

+ or - 10 degrees of horizontal, both

parallel to the air flow and at the right

angle of air flow. The control side of the

terminal is labeled with an arrow

indicating UP. The first letter of the

model number (P) indicates pneumatic

controls. Most electronic units (A-analog

controls and D-digital controls) can be

installed in any orientation. Check with

the local TITUS representative for

verification.

Duct Connections

Slip each inlet duct over the inlet collar

of the terminal. Fasten and seal the

connection by the method prescribed by

the job specification.

The diameter of the inlet duct "D" in

inches must be equal to the listed size

of the terminal; e.g. a duct that actually

measures 8 inches must be fitted to a

size 8 terminal. The inlet collar of the

terminal is made 1/8 inch smaller than

listed size in order to fit inside the duct

(see Figure 1). The supply ductwork

must be insulated up to the face of the

terminal unit even if inlet adapters are

used.

Note:

Do not insert duct work inside

the inlet collar. Inlet duct should be

installed in accordance with SMACNA

guidelines.

The outlet end of EDV and MDV series

units are designed for use with slip and

drive duct connections. A rectangular

duct the size of the terminal outlet

should be attached.

If single-point electronic velocity sensors

are used, 3 to 5 inlet duct diameters of

straight duct should be provided at the

terminal inlet; for specific guidelines,

consult the control manufacturer’s

installation guidelines. Sensor(s) may be

attached to th e i n s i d e o f c o n t r o l

enclosure for protection during shipping.

Sensors must be inserted in inlets and/

or discharge duct of terminal before

operating. Remove any protective

plastic devices from tip of sensor before

installation.

Figure 1. Dual Duct Recommended Hanger Bracket Locati ons

Hanger Bracket

Location or

Hanger Strap

2" Typical

1/2"

D

Option.