Aerocross sensor - calibration curves – Titus QCV IOM User Manual
Page 2
Advertising
QCV-IOM-1.0 2-28-13
Unit
Damper
Size
SQ FT
CFM
FPM Quantity Size
A
0.174
320
1837
1
4/5
B
0.250
477
1908
1
4/5
C
0.333
629
1890
1
4/5
D
0.555
1047
1886
1
8
E
0.778
1539
1978
1
8
F
0.750
1472
1962
2
4/5
G
0.833
1676
2012
1
10
H
1.250
2619
2095
2
10
J
1.500
3036
2024
1
12
K
1.944
4385
2256
1
16
L
2.500
5582
2233
2
12
M
2.444
5847
2392
1
16
N
3.000
7413
2471
1
16
P
4.167
11224
2693
2
16
R
5.555
16496
2970
2
16
K-Factor
Sensor
AeroCross Sensor - Calibration Curves
Inlet Sensor Applications (For QCV's)
P = Differential Pressure On AeroCross,
IN WG
K = Flow Required To Produce A 1.0 IN WG
Differential Pressure On AeroCross,
CFM
CFM = K P
P = CFM
K
2
Equations: