Titus Pneumatic Controls IOM User Manual

Installation manual

Advertising
background image

Adjusting Minimum and Maximum Air Flow

Airflow limits are printed on the label on the

optional controller cover (or the side of the

terminal) and the side of the controller (Figures

2 and 3).

If field adjustment becomes necessary, follow

the procedure outlined below.

AIR FLOW ADJUSTING PROCEDURES FOR

ALL CONTROLLERS

1. Remove the optional controller cover

(Figure 1).

2. The action of the controller must match the

settings printed on the labels (Figures 2

and 3).

a. TITUS I—Direct acting, normally

open, (control color—beige).

b. TITUS I—Reverse acting, normally

closed, (control color—gray).

c. TITUS IIA—Direct or reverse acting

thermostat. No adjustment necessary.

d. TITUS IIA—Verify setting on damper

dial is correct (N.O. or N.C.).

e. TITUS II—Check thermostat and

damper compatibility selectors, verify

that settings are as marked on the

label.

3

Remove the caps from the tees in the HI

and LO tubes (red and green stripe).

Connect a manometer gauge to both tees

(gauge with a 0 to 2 inch scale is

recommended).

4. Refer to the calibration curve for the size

terminal being serviced (Page 8). From the

curve read the differential pressure across

the sensor for the required airflow.

5. For instructions to readjust the control refer

to:

a. TITUS I See page 3.

b. TITUS IIA See page 4-5.

c. TITUS II See page 6-7.

d. For dual duct terminals, see document

PNEU-DD-IOM.

e. Quick-Check. See page 2.

6. After the flow rates are adjusted:

a. Replace the thermostat connection to

the controller.

b. Remove the gauge and replace the

caps on the tees.

c. Replace the optional controller cover.

Figure 1. Adjusting Air Flow

Figure 2. Unit Label

(See Figure

3)

(Label, See Figure 3)

MODEL NO: PESV

TOTAL CFM: 600

TITUS II NO RA COOL

MIN. CFM: 160

FACTORY NO:XXXXX

SIZE: 08

VP: .410

VP: .030

ITEM: 1

Figure 3. Controller Label

Installation Manual

PNEU-IOM-1.0

5-2-05

TITUS I, II, and IIA Pneumatic Controls

Installation, Operation, and Maintenance Manual