Installation Manual - TAF-L Perimeter System

TAF-L Perimeter System IOM

Redefine your comfort zone. ™ | www.titus-hvac.com

The TAF-L underfloor perimeter system consists of a series of plenum
boxes under linear runs of CT-TAF-L diffuser along the perimeter of a
building. The TAF-L-V plenum provides cooling, the TAF-L-W provides
heating, and the TAF-L-R provides a return.

The TAF-L-V cooling unit has a variable linear bar diffuser with a series of
apertures through which the air exits. The TAF-L-W heating plenum has
a hot water fin tube heater assembly in the plenum.

The CT-TAF-L core itself has a specific wing configuration designed to
deflect the air and provide throw reduction. Figure 1 below shows all the
major components of the system and their typical installation.

CT-TAF-L Diffuser Core

TAF-L-W Heating Plenum

Blankoff Plates As Needed

To Fill Space Between Plenums

CT-TAF-L Diffuser Frame

TAF-L-V Cooling Unit

with Actuated Aperture Plates

TAF-L-R Return Plenum

20" X 8" Opening For Butt

Connected Rigid Duct

Rigid Duct From Return Plenum

To Fan Box (Supplied By Others)

Pedestal

Perimeter Diffuser Assembly

Carpet

Floor Tile

Baseboard

Wall

Figure 1 - Typical Finished Installation

TAF-L Underfloor Perimeter System