2.5 Series Connections

Series connections can lead to high voltages and should be carefully configured by

experienced and qualified personnel only. Please refer to proper codes and guidelines for

safe installation. Refer to the latest edition of the National Electric Code for additional

details. For series installations, it is recommended a cutoff voltage be set to 23.25V per

series module.

Ultralife suggests contacting the factory for assistance when connecting MKMs in series,

as external diodes may be required, as well as proper fusing and protection for safety.

2.6 Environmental Controls

Although the Lithium batteries in the MKM series are extremely robust, it is suggested they

be used in a controlled temperature atmosphere of between 5C and 45C for optimum

performance. Environmental exposure outside of these limits will result in decreased

overall performance and possible decrease in cycle life.