Weidmuller WI-MOD-945-E: 900Mhz Wireless Ethernet & Device Server v1.9 User Manual

Wi-mod-945-e wireless ethernet, Installation guide, Fcc statutory requirements

Advertising
background image

FCC Statutory Requirements

Unlicensed operation limits the radio power. High gain aerials may only be

used to compensate for cable losses.

RJ-45 Ethernet

Connection

Factory

Default Switch

RS485 Resistor

Termination

Switch

1

2

8

9

7

6

4

5

3

Connect M4 screw terminal on
rear of module to GROUND for

surge protection

*

Installation Guide

REV 1.9

December 2011

WI-MOD-945-E Wireless Ethernet

*

Connect to Ground as

close as possible to the

module.

NOTES

ALL connections must be SELV (Safety Extra Low Voltage <50V AC & <120V DC)

Ethernet Port wiring is that of a hub or switch.

‘-' Supply terminal and 'M4 GND screw on rear of module' must be connected to EARTH /
GROUND as close as practical to the unit.

Module Power Supply -Ve terminal is not Isolated from Earth/GND

DIO channel can be wired as either input or output.

Care must be taken with antenna selection and proximity to the radio.

For short distance paths, RX signal level should be checked and if it exceeds -40dBm a 20dB
attenuator must be fitted in line with coax cable.

Demo Antennas must not be used for final installation.

The non-metallic cover of the Wireless Ethernet Modem is considered to constitute an
electrostatic discharge hazard. Clean only with a damp cloth

The Wireless Ethernet Modem enclosure contains aluminum and is considered to constitute a
potential risk of ignition by impact or friction and must be taken into account during installation.

If the Wireless Ethernet Modem is installed as Category 3 equipment, then it shall be installed
in an Enclosure which maintains an ingress protection rating of IP54 and meets the enclosure
requirements of EN 50014 or EN60079-0.

If installed in a hazardous environment coaxial cable shall be installed in a metallic conduit as
per NEC requirements

9-30V

DC Supply

*

2A Fuse or

Circuit Breaker

BEWARE OF

GROUND LOOPS

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A,B,C AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

RS232 Connections

DCE HOST

DB9

MALE

MODEM

DB9

MALE

RD

TD

SG

RTS

CTS

DSR

DTR

DCD

RD

TD

SG

RTS

CTS

DSR

DTR

DCD

2

5

7

8

6

4

1

3

2

5

7

8

6

4

1

3

DCE HOST

MODEM

DB9

MALE

DB9

FEMALE

RD

TD

SG

RTS

CTS

DSR

DTR

DCD

RD

TD

SG

RTS

CTS

DSR

DTR

DCD

2

5

7

8

6

4

1

3

2

5

7

8

6

4

1

3

PC’s

PC’s, Dataloggers

RS485 Connections

HOST

HOST

-

+

Antenna Installation

COLINEAR

ANTENNA

MAST

MODULE

SURGE

ARRESTOR

(RECOMENDED)

COAXIAL CABLE

WEATHERPROOF

CONNECTORS WITH

“3M 23” TAPE

PROVIDE GOOD GROUND

CONNECTION TO MAST, MODULE

AND SURGE ARRESTOR

CONNECTION ON

REAR OF MODULE

1 Wavelength

minimum

IF GROUND CONDITIONS ARE

POOR, INSTALL MORE THAN

ONE STAKE

STRESS RELIEF

LOOP

M4 x 5mm

INSTALL ANTENNA ABOVE

LOCAL OBSTRUCTIONS FOR

MAXIMUM RADIO DISTANCE

Wavelengths

900 MHz = 33 cm

Digital Output Wiring

Max

30VDC

0.5A

-

+

DC Load,

eg Relay

MODULE

COM

DIO

*

*