Not UL listed

Occurs with short delay time adjustment set at I.

The Molded Case Switch has a fixed non-interchangeable rating plug

Ground Fault Protection: When selected, ground fault
pick-up and time delay settings shown in Table 1-2 allow
selective ground fault coordination with other circuit pro-
tection devices.

Ground Fault Alarm Unit: A ground fault alarm unit may
be used with the trip unit to provide visual indication and
a contact closure when a ground fault trip occurs. The
ground fault trip alarm unit is ordered and shipped sepa-
rately if required.

DC Application: N-Frame trip units are suitable for AC
application only.

Field Testing: Test points are available for functional field
testing of the trip unit when connected to test kit.

Internal Accessories: Internal accessories mount on
the Digitrip trip unit. A list of internal accessories and
their instruction leaflets is provided below:

• Alarm (Signal)/Lockout (ASL) Switch 40752-094
• Auxiliary Switch 40752-097
• Shunt Trip 40752-095

Note: Shunt trip and undervoltage accessories, if
required, must be mounted in the left pole.

Note: N-Frame trip unit versions with ground fault
protection are supplied with an auxiliary switch,
mounted in the right pole of the trip unit.

TABLE 1-2: ELECTRONIC TRIP UNIT FUNCTION AND RATING SENSING

Trip Function

Rating/Setting Description

Ampere Rating
Fixed at 100%

Fixed rating plugs available

Trip Unit Ampere Rating

Fixed Rating Plugs

1200 Amp
800 Amp

600, 630

, 700, 800, 1000, 1200, 1250

A (I

n

)

400, 450, 500, 550, 600, 630

, 700, 800A (I

n

)

Adjustable Long
Time Pick-up

Adjustable rating plugs
available

Trip Unit Ampere Rating

Adjustable Rating Plugs

1200 Amp
800 Amp

600,800,1000,1200A (I

n

)

400,500,600,800A (I

n

)

Short Delay Pick-up (Adjustable)

In multiples of installed rating plug amperes (I

n

) with marks at 2-3-4-5-6-7-8x

Short Delay Time (Fixed)

I

2

t ramp configuration

Short Delay Time (Adjustable)

Flat response with time delay settings at 100 ms, 200 ms, and 300 ms

Instantaneous Pick-up

In multiples of installed rating plug amperes (I

n

) with marks at 2-3-4-5-6-7-8x

Ground Fault
Pick-up
(adjustable)

Trip Unit Ampere Rating

Trip Unit Setting

1200 Amp
800 Amp

200, 400, 600, 800, 1000 and 1200 Amp
200, 400, 600, 800, 1000 and 1200 Amp

Ground Fault Time Delay

Settings at instantaneous (I) 150 ms, 300 ms, and 500 ms

40752-093(1)

Effective 5/02

• Undervoltage Release Mechanism