140mg-i magnetic only trip unit, 140g-i thermomagnetic trip unit, Clack – Rockwell Automation 140G-Ix Installation Instruction User Manual

Page 3

Advertising
background image

F

C

D

B

E

H

G

A

I

4

140MG-I MAGNETIC ONLY TRIP UNIT

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.

DIR 1000720R0001 (L5141)

Publication 140G-IN095A-MU-P - April 2013

Manually trip the breaker prior to adjustment of the
magnetic settings.

E’obbligatorio mettere l'interruttore in posizione Trip
test prima di regolare il termomagnetico.

Der Leistungsschalter muss vor Einstellung des
thermomagnetischen Auslösers zwingend in die
Prüfstellung geschaltet werden.

Il est obligatoire de mettre le disjoncteur en position de
Test de Déclenchement avant de régler le déclencheur
magnétothermique.

Es obligatorio situar el interruptor en posición “Test de
Disparo” antes de realizar el ajuste del relé
termomagnético.

In

A

B

C

D

E

F

G

H

I

100

600

675

750

825

900

975

1050

1125

1200

110

660

743

825

908

990

1073

1150

1238

1320

125

750

844

938

1031

1125

1219

1313

1406

1500

150

900

1013

1125

1238

1350

1463

1575

1688

1800

I3

USE FLAT PLATE
SCREW DRIVER

140G-I THERMOMAGNETIC TRIP UNIT

1000

I1(4)

100

5

Fixed
Fixed
Fixed
Fixed

Fixed

In

I1

I3

60
63
70
80

Fixed
Fixed
Fixed
Fixed
Fixed
Fixed

Fixed
Fixed

175
200
225

60

600

63

630

70

700

90

100
110
125
150
160

800

90

900

100

1000

225

2250

Type

160

1600

175

1750

200

2000

110

1100

125

1250

150

1500

80

In=100A

I3(4)

CLACK

1

2

In=200A

A

B

C

D

E

I3

F

G

H

I